Supply temperature display
CO
required (ppm) 0 – 99 x 10 ppm
2
CO
allowed difference 0 – 99 x 10 ppm
2
SET Temperature 150 – 350 (/10)
SET Fan speed (%) 0,20 - 100
SET Fan speed fixed 0 - 4
SET Pressure 0 – 999 Pa
Display supply temperature - 500 – 1000 (/10)
Save parameters 0: No
Current fan speed (%) 0 – 100 %
Current fixed fan speed 0 – 4
Temperature Setpoint 150 – 350 °C (/10)
Current Temperature - 500 – 1000 (/10)
Pressure Setpoint 0 – 999 Pa
Current pressure 0 – 999 Pa
CO
Alarm 1 address 0/1
Alarm 2 address 0/1
Alarm 3 address 0/1
Alarm 4 address 0/1
Alarm 5 address 0/1
Alarm 6 address 0/1
Alarm 7 address 0/1
Alarm 8 address 0/1
Alarm 9 address 0/1
Alarm 10 address 0/1
To save configuration parameters, write 22 to the register 49, then settings are saved to EEPROM mem-
ory, controller reloads.
48
0: Off
Sound
1: 1 – 9 sound tone
0: Not shown
1: Shown interchangeably with
the set temperature
22: Yes
Setpoint 0 – 999 ppm
2
Current CO
0 – 999 ppm
2
Holding
0x2A
register
Holding
0x2B
register
Holding
0x2C
register
Holding
0x2D
register
Holding
0x2F
register
Holding
0x30
register
Holding
0x31
register
Holding
0x32
register
Holding
0x34
register
Holding
0x36
register
Input register
0x01
Input register
0x02
Input register
0x03
Input register
0x04
Input register
0x05
Input register
0x06
Input register
0x07
Input register
0x08
Coil
0x01
Coil
0x02
Coil
0x03
Coil
0x04
Coil
0x05
Coil
0x06
Coil
0x07
Coil
0x08
Coil
0x09
Coil
0x0A
www.salda.lt
40
41
42
43
44
45
46
47
48
49
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10