Temperature
• In controller, desired temperature can be set between 15 °C and 35 °C
• Supply air and set temperatures can be displayed interchangeably (set temperature is displayed for 5 seconds,
then supply air temperature is displayed for 2 seconds)
Remote control (Modbus)
Controller supports fully configurable Modbus interface. Panel can operate as master and slave device in mod-
bus network and also it can be fully controlled and configured not only via service menu but also via modbus
interface.
User menu
In order to reach user menu, press down B2 and B3 for 3 seconds.
In user menu, menu items (P.01, P.02 etc.) settings are displayed sequentially. Menu item is selected using ele-
ments B4 and B6. After pressing B5, value of selected parameter is shown and can be changed using elements
B4 and B6. Press B5 to save the parameter and to return to menu.
Due to limitations of segment display, values of P.04 and P.05 are shown divided by 10, i.e. if 20 is displayed, it
means that real value is 20 x 10 = 200.
.6 - To reset filter timer to press and hold for 5 seconds item B5. Also filter timer resets by removing .3 alarm.
Touch element B1 to exit menu.
No.
.
.
Supply air temperature display
.3
.4
.5
.6
Intended use
1) Modbus master (main)
This controller can control other devices (controlled by MODBUS protocol) for example, air handling units. This
can be set in service menu by selecting required parameters for service menu items F.17, F.18, F.19, F.20, F.21.
To control not only standard devices, select "CUSTOM" in menu item F.20 and device addresses in menu items
from F.22 up to F.37. If devices have no such addresses, in fields of given menu items enter "00:00". Normally,
this controller is used with ECO or PRV control boards.
42
Name Possible values
0 - Off
Sleep mode
1 - 99 sleeping time in seconds
Sound 0: Off
1: 1 – 9 sound tone
0: Not shown
1: Shown interchangeably with the set temp
CO
required (ppm) 0 – 99 x 10 ppm
2
CO
allowed difference 0 – 99 x 10 ppm
2
Displaying number of days from the last
Filtrer timer
change of the filters
MODBUS
CONTROLLER
(master)
AHU
(slave)
Default
value
0
2
0
20 x 10
5 x 10
0
www.salda.lt