Inputs and outputs

Inputs and outputs
Changes to the standard configuration:
No.
Input
Solar inflow secondary circuit ("T.Solar Pre2"/TSV) The
S5
inflow temperature sensor of the secondary solar cir-
cuit, required for recording solar yields.
Solar return secondary circuit ("T.Solar Ret2"/TSR) The
S6
return temperature sensor of the secondary solar cy-
cle, required for recording solar yields.
Solar inflow primary circuit ("T.Solar Pre1"/RF2)
S16
The inflow temperature sensor of the primary solar cir-
cuit, required for recording solar yields.

Additional functions

Changes to the standard configuration:
Fct.
Function
No.
COMPARISON
26
DIFF FUNC.2
PID CONTROL PID
27
SOLAR2
LOGIC FUNCTION
28
OR2
ANALOG FUNCT
29
ANALOG
Transfer of the boiler temperature to modulating external boilers
You can transfer the required boiler temperature to a mod-
ulating external boiler as a voltage signal with functions
28 and 29 using Output A15.
In the "Outputs" menu, Output A15 must be set with the
appropriate scaling.
6
Explanation
Compares the inflow (pre-run) temperature in the primary circuit "T.Solar Pre1" (sensor S16
or RF2) with the storage tank reference temperature "T.Ref.Sto" (sensor S3 or T4) to enable
the solar pump in the secondary circuit ("Solar Pump2").
"Solar Pump2" switches on, if:
- "Solar Pump1" is on and "T.Solar Pre1" > "T.Ref.Sto" + 10K
"Psolar Pump2" switches off, if:
- "Solar Pump1" is off or "T.Solar Pre1" < "T.Ref.Sto" + 7K
Controls the speed of the solar pump "Solar Pump2" in the secondary circuit: The speed of
the pump is controlled so that "T.Solar Pre2" is 5 Kelvin below that of "T.Solar Pre1".
Status request for heating and WW request.
Determines each of the important target temperatures (nom. temperatures) using the func-
tions "MAX(AN)" and "WW_REQ".
No. Output
"Solar Pump1"/Psolar
A1
The speed of the solar pump in the primary circuit
is controlled in the "AUTO" setting.
"Solar Pump2"/Opt.2
A7
The speed of the solar pump in the secondary cir-
cuit is controlled in the "AUTO" setting.
Standard settings for scaling:
150 scale division (= 15 °C) is supplied with 0.6V and
900 scale division (= 90 °C) is supplied with 10.0V.
You can only change the scaling in the "Expert" operating
mode.
M 70-M – Subject to technical changes 11.06