1.2.5.

Authorized batteries

Use batteries with a capacity of 86 to 225 Ah (daughter board jumper on '75').
-
For using 38 to 225Ah battery capacities in 24V, put daughter board jumper on '50'. In this case,
-
Imax b = 100A (mains not present) and the threshold of 13mΩ±10% becomes 20mΩ±10%.
For using 65 to 225Ah battery capacities in 48V, put daughter board jumper on '50'. In this case,
-
Imax b = 100A (mains not present) and the threshold of 26mΩ±10% becomes 40mΩ±10%.
Use Yuasa, Powersonic, ABT, Enersys, Effekta, or Long brand batteries. If you would like to use another
-
battery brand, please have them approved.
2.1.

Mounting

Note: When installing the module in the rack, the protection rating must comply with fire safety standards EN 54-4/A2: