7. Troubleshooting

WARNING:
All the maintenance work listed below must be executed with the electricity switched
off, i.e. plug pulled out.
PROBLEM
Motor does not run
Motor runs, but wheel only
turns irregularly or jolts
Device vibrates excessively
U = User
HS = HEYLO Service
Contact your local dealer for spare parts and service or the HEYLO Customer Service
Department. We would be glad to help you!
Your HEYLO Customer Service:
Tel.
+49 (0) 42 02 – 97 55 15
Fax
+49 (0) 42 02 – 97 55 97
Email service@heylo.de
CAUSE
No power to the device
Switch not turned on
Blower wheel blocked
Air inlet or outlet
Switch interrupted
Wire loose
A strong jolt bent the motor
suspension, so that the wheel is
jammed.
A strong jolt has caused the
motor
to
slip
out
of
suspension, so that the wheel is
jammed.
Accumulation of dirt on the
wheel
Blower wheel out-of-balance
Bent blower wheel
Bent motor shaft
23
Exec
SOLUTION
ution
U
Connect device, check fuse, turn on switch
U
Remove reason for blockage
U
Switch off machine and let it cool; then remove
blockage
HS
Request replacement switch from the dealer or
from HEYLO.
HS
Check wiring and tighten if necessary.
HS
Dismantle the motor from the housing, then
replace bent motor suspension or repair it.
Dismantle motor from the housing, then insert
HS
motor correctly into the suspension.
the
U
Clean blower wheel
HS
Balance or replace blower wheel
HS
Change blower wheel
HS
Change motor