Regler für zuluft- oder raumtemperaturregelung, ein ausgang 0-10v.
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

AQUA24A1/D
TG-K360
1
2
3
4
5
6
7
AQUA
Fig 4
TBI-100
3
6
+
2
0
1
10
9
AQUA
Fig 5
9
1
0
+
2
3
10
AQUA
TBI-100
Fig 6
Box 116 428 22 KÅLLERED SWEDEN
Tel +46 (0)31 720 02 00
Fax +46 (0)31 720 02 50
INSTRUCTION
Settings
AQUA24A1/D is on delivery set to values suitable as starting values
for balancing the system.
Final settings must be tried out when the system is comissioned.
Factory settings FS in brackets.
Setpoint Setpoint for the main controller. 0...30°C. (FS 20°C).
Pd
Proportional band for the duct controller. 2...100K.
(FS 18K). The value signifies the necessary change in
duct temperature to shift the output from 0V to 10V.
Id
Reset time for the duct controller. 1.7...20 minutes.
(FS 8 minutes).
CF
Cascade factor. 0.5...15. (FS 5).
The value signifies the immediate change in duct con-
troller setpoint for a 1K step change in room tempera-
ture. (Cascade control only).
Ir
Reset time for the room controller. 3...33 minutes
(FS 20 minutes) (Cascade control only)
Min
Minimum duct temperature. 0...30°C.
(FS 15°C). (Cascade control only).
Max
Maximum duct temperature. 20...60°C.
(FS 40°). (Cascade control only).
N.B. When running single sensor room temperature control (not
cascade control) CF, Ir, Min and Max are inactive.
Amplification and reset time are then set as for duct tempera-
ture control using Pd and Id.
Function switches
1
Position A: Built-in setpoint.
Position B: External setpoint.
2
Position A: Y1 increasing output signal on increasing cooling
demand.
Position B: Y1 increasing output signal on increasing heat
demand.
3
Position A: P-control, duct controller (room controller on
single-sensor room control).
Position B: PI-control, duct controller (room controller on
single-sensor room control).
4
Position A: P-control, room controller when running cascade
control.
Position B: PI-control, room controller when running cascade
control.
5
Position A: Duct temperature control or single sensor room
control.
Position B: Cascade control
INSTRUCTION
Wiring diagrams
Fig 1: Main sensor when using the built-in setpoint.
Fig 2: Main sensor and external setpoint TBI-30.
Fig 3: Main sensor and external setpoint when running room
temperature control with room sensor TG-R430.
Fig 4: Limiting sensor when running cascade control.
Fig 5: Minimum limiting of the output signal using limiting
potentiometer TBI-100.
Fig 6: Maximum limiting of the output signal using limiting
1
Main sensor
2
Limit sensor
3
Not connected
4
Signal neutral
5
Signal neutral
6
+10V DC
7
0-10V in
8
SPC 0-10V DC in
9
Signal neutral
10
Y1
Output 0-10V DC
All neutrals are internally
11
Signal neutral
connected
12
Signal neutral
13
Neutral
14
24V AC in
15
Fan supervision
16
Signal neutral
17
Inverter in
18
Inverter out
19
Not connected
20
Not connected
21
Not connected
22
Not connected
23
Not connected
24
Not connected
EMC emissions & immunity standards
This product conforms with the requirements of European EMC
standards CENELEC EN 50081-1 and EN 50082-1 and carries
the CE mark.
External
setpoint
Supply
voltage