Herunterladen Inhalt Inhalt Diese Seite drucken

Declaration Of Conformity - Emerson FloBoss 107 Anleitung

Durchfluss-computer
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 9
Emerson FloBoss™ 107 Flow Manager
Figure 1. FloBoss 107 Flow Manager Nameplate
(ATEX Version shown)
Use this safe use instructions (SUI) document with the
FloBoss 107 Flow Manager Instruction Manual (part
D301232X02). For full cautions and descriptions of
installation and troubleshooting procedures, refer to that
manual.
FloBoss 107 special conditions for Safe Use
Connections made to the LOI (D-type connector) port
shall be mechanically secured in place with suitable
screw connections to prevent loosening or
disconnection during use.
When using Ethernet connections, the Enhanced
Communications module's RJ45 (Ethernet)
connection must have a mating connector with a valid
securing clip to prevent loosening or disconnection
during use.
The USB connector on the Enhanced Communications
module shall not be used unless the area is known to
be non-hazardous (non-flammable).
Install the FB107 within a suitable certified ATEX or
IECEx approved IP54 or better enclosure.
The area in which the equipment is used should be a
minimum of Pollution degree 2, as defined by EIC
60664-1 (that is, the environment should not contain
conductive pollution and the equipment shall be
installed in an indoor or sheltered location).
The equipment may be used in zone 2 with flammable
gases.
The equipment may be used in the presence of
flammable gases and vapors with apparatus groups
IIC or IIB or IIA and with temperature classes T1 or T2
or T3 or T4.
The equipment is certified for use in ambient
temperatures in the range of –40C to +75C and
should not be used outside this range.
The equipment is to be installed by suitably trained
personnel in accordance with the applicable code of
practice (typically IEC EN 60079-14).
Remote Automation Solutions
Safe Use Instructions – Emerson FloBoss 107 Flow Manager
The equipment does not require assembly or
dismantling.
With regard to safety it is not necessary to check for
correct operation.
No user adjustment is required.
Regular periodic inspection of the equipment should
be performed by suitably trained personnel in
accordance with the applicable code of practice to
ensure it is maintained in a satisfactory condition.
The equipment is not intended to be repaired by the
user. Repair of the equipment is to be carried out by
the manufacturer, or their approved agents, in
accordance with the applicable code of practice.
The equipment contains no other customer-
replaceable parts.
Under certain extreme circumstances, the non-
metallic parts incorporated in the enclosure of this
equipment may generate an ignition-capable level of
electrostatic charge. Therefore, the equipment shall
only be cleaned with a damp cloth.
If the equipment is likely to come into contact with
aggressive substances (such as acidic liquids or gases
that may attack metals or solvents that may affect
polymeric materials), then it is the responsibility of
the user to take suitable precautions that prevent it
from being adversely affected, thus ensuring that the
type of protection is not compromised.

Declaration of Conformity

Hereby, Remote Automation Solutions declares that the
FloBoss 107 product is in compliance with the essential
requirements and other relevant provisions of European
Directives 2014/30/EU (EMC) and 2014/34/EU (ATEX).
DANGER
When installing units in a hazardous area, make sure
all installation components selected are labeled for use
in such areas. Installation and maintenance must be
performed only when the area is known to be non-
hazardous. Installation or maintenance in a hazardous
area could result in personal injury or property
damage.
Always turn off the power to the FloBoss before you
attempt any type of wiring. Wiring powered
equipment could result in personal injury or property
damage.
To avoid circuit damage when working inside the unit,
use appropriate electrostatic discharge precautions,
such as wearing a grounded wrist strap.