Herunterladen Inhalt Inhalt Diese Seite drucken

SOMFY animeo KNX RS485 Gebrauchsanweisung Seite 7

Motor controller wm
Vorschau ausblenden Andere Handbücher für animeo KNX RS485:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
EN
A
PICTURES
[1] KNX RS485 Motor Controller WM,
wall mounted version (ref. 1860286)
B
MOUNTING
Choose the optimal location: flat and large surface,
open the housing.
[1] Mount the KNX RS485 Motor Controller WM
[2] Mount the DIN rail version
1.
Vertical
2.
Horizontal
C
WIRING
[1] Finish wiring and connect KNX bus, keep
minimum distance
[2] Wiring diagram
[3] Check the correct running directions of the end
product
UP: the end product goes up g
STOP: the end product stops g h
DOWN: the end product goes down h
CHARACTERISTICS
Supply voltage from KNX bus
Rated current consumption KNX
Supply voltage of local push buttons
Terminals
Operating temperature
Relative humidity
Material of housing
Housing dimensions (w x h x d)
Degree of protection
Protection class
Pollution degree
CABLE
Connection to ...
RS485 bus
Modular Jack 8P4C (RJ45)
KNX bus
D
KNX voltage 21...32 V DC, SELV
As per KNX guidelines, <= 12.5 mA
SELV, 16 V DC ⎓
RJ45
- 5 ° C to 50 ° C
Max. 85 %
PC-ABS
90 x 180 x 45 mm
IP 20
III
2
Cable
Min.: 4 x 2 x 0.5 mm/24 AWG
2 x 0.8 mm/20 AWG
CONFIGURATION
[1] KNX Prog button
Wall mounted version
[2] Topology
1.
The stub must not exceed 10 m.
2.
The length of the RS485 bus must not
exceed 200 m.
3.
Not more than 18 RS485 motors may be
connected together.
RS485 motors can be connected via
bridging adapter. Different motor types can
be used.
H RS485 Terminator is mandantory even if
only one motor is connected.
Twisted pair
Required twisted pair shielded,
impedance 100 Ω (-10 Ω/+30 Ω),
recommended CAT5-FTP,
following Somfy RS485 guidelines
Required, following
KNX topology guidelines
animeo KNX RS485 MOTOR CONTROLLER . REF. 5127869B -
Max. length
200 m
-
7/16

Werbung