Herunterladen Inhalt Inhalt Diese Seite drucken

SOMFY animeo Connect Gebrauchsanweisung Seite 7

Vorschau ausblenden Andere Handbücher für animeo Connect:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 6
EN
A
MOUNTING
[1] Wall mounted
[2] DIN-rail mounted
B
WIRING
Complete the wiring and connect 24 V DC Power Supply
[1] Wiring diagram
A. USB stick (input/output) max. 150 mA
(for maintenance or remote access)
B. LAN (input/output)
C. IP Bus (input/output)
D. Green = boot process or power
Red = malfunction or update process
E. PROG: Not active
The cable used for the IP Ethernet connection must be a
shielded cable. The shield needs to be connected on both
ends.
n Not compatible with PoE switch.
[2] Topology
CHARACTERISTICS
Supply voltage
Power Supply
Minimum current
Max. current
Minimum power
Minimum power (primary)
RTC
USB
Current with 1 x USB, 2 x Ethernet *
Current with 2 x USB **
Battery
Operating temperature
Relative humidity
Material of housing
Housing dimensions (w x h x d)
Protection class
Degree of protection
Conformity
* USB stick = 2 GB Kingston / ** 2 x original Somfy <USB sticks
CABLE
Connection to ...
Power Supply
Ethernet
We care about our environment. Do not dispose of the appliance with usual household waste. Give it to an approved collection point for recycling.
24 V DC +/- 10 % SELV/1 A max.
Mandatory use of certified power supply with limited power (certified according to the
relevant version of 60950-1 or 62368-1, EN/IEC or UL as needed in the country of use).
Limited power classified as LPS, PS2 or UL class II (according to standard).
50 mA
360 mA@24 V
1.2 W
1.2 W
+/- 3 min/year
2 x USB 2.0, each 5 V/500 mA
90 mA@24 V
77 mA@24 V
CR1220
- 5° C...+ 50° C
85 % at 30 ° C
ABS
133 x 86 x 44 mm
III
IP20
www.somfy.com/ce
Cable
Cat. 6
C
COMMISSIONING AND OPERATING
Complete installation of all devices.
Connect the PC to the IP input (C.).
Run the animeo Connect Operating Software and follow
the procedure described in the software guide.
A.
„xx" represents the bus system handled by the
gateway, e.g. io, SDN, ...
D
BATTERY
The battery included in this product (CR 1220) is
designed to last throughout the product's lifetime and is
not foreseen to be replaced. Only qualified electricians
are to remove and dispose the battery correctly at the
end of life of the product.
m Batteries or accumulators must be separated from
other types of waste and must be recycled through
your local waste treatment and recycling system.
Twisted pair
animeo Connect . Connect Main Controller . Ref. 5137981A -
Max. length
1.8 m
100 m
8/20