Herunterladen Inhalt Inhalt Diese Seite drucken

SOMFY CONTROL BOX 3S io Bedienungsanleitung Seite 50

Vorschau ausblenden Andere Handbücher für CONTROL BOX 3S io:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 23
Meaning of different parameters
Code Description
Values (bold = default)
P01 Complete cycle operating
0: sequential
mode
1: sequential + timed close
2: semiautomatic
3: automatic
4: automatic + cell blocking
5: deadman's control (wire)
P02 Complete operating mode
0 to 30 ( time delay value = value x 10 s)
automatic timed closing
2: 20 s
P03 Pedestrian cycle operating
0: ident. to complete cycle operating mode
mode
1: without automatic closing
2: with automatic closing
P04 Short automatic closing
0 to 30 ( time delay value = value x 10 s)
time delay in pedestrian
2: 20 s
cycle
P05 Long automatic closing
0 to 99 ( time delay value = value x 5 min)
time delay in pedestrian
0: 0 s
cycle
P07 Cell safety input
0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power supply switching
4: bus cells
P09 Programmable safety input 0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power supply switching
P10 Programmable safety input
0: active closing
- function
1: active opening
2: active closing + ADMAP
3: all movement disabled
P11 Programmable safety input
0: stop
- action
1: stop + partial reversal
2: stop + complete reversal
P12 Orange warning light
0: no warning
1: with 2 s warning prior to movement
P13 Area lighting output
0: inactive
1: controlled operation
2: automatic + controlled operation
P14 Area lighting time delay
0 to 60 (time delay value = value x 10 s) - 6: 60 s
operating code display
Code Description
C1
Awaiting command
C2
Gate opening
C3
Awaiting gate closure
C4
Gate closing
C6
Detection in progress for cell safety
C8
Detection in progress for programmable safety
C9
Detection in progress for emergency stop safety
C12
Current reinjection in progress (Control Box 3S Axovia only)
C13
Safety device autotest in progress
C14
Permanent complete opening wire control input
C15
Permanent pedestrian opening wire control input
C16
BUS cell programming refused
Cc1
9.6 V power supply
Cu1
24 V power supply
Fault and breakdown code display
Code Description
E1
Cell safety autotest fault
E2
Programmable safety autotest fault
E4
Obstacle detection when opening
E5
Obstacle detection when closing
E6
Cell safety fault
E8
Programmable safety fault
E9
Thermal protection
E10
Motor short circuit protection
E11
24V power supply short protection
E12
Hardware fault
E13
Accessories power supply fault
E14
Intrusion detection
E15
Fault when the control box supplied by the
backup battery is first switched on
Access to memorised data -
Data
Description
u0 to u1
Complete opening cycle counter
u2 to u3
u6 to u7
Cycle counter with obstacle detection
u8 to u9
u12 to u13
Partial opening cycle counter
u14 to u15
Reset movement counter
u20
Number of monodirectional remote controls memorised for complete opening control
u21
Number of monodirectional remote controls memorised for pedestrian opening control
u22
Number of monodirectional remote controls memorised for remote lighting control
u23
Number of monodirectional remote controls memorised for auxiliary output control
u24
0 = no system key present, 1 = system key present
d0 to d9
Log of the last 10 faults (d0 most recent - d9 oldest)
dd
To clear the fault log: press and hold "ok" for 7 s.
Setting
compl.
Comments
The cell autotest is not satisfactory.
The programmable safety input autotest is not
satisfactory.
Detection in progress on safety input for longer than
3 minutes.
Thermal protection is correct
Short circuit protection for input/outputs: product and
additional devices connected to terminals 21 to 26
(orange light, photoelectric cells (except BUS), code
keypad) not operating
The hardware auto tests are not satisfactory
The accessories power supply cuts out following an
overload (excessive consumption)
Current reinjection function
To access memorised data, select parameter "ud" and press "ok".
global [Hundred thousands - ten thousands - thousands] [hundreds - tens - units]
since last auto-programming [Hundred thousands - ten thousands - thousands] [hundreds - tens - units]
global [Hundred thousands - ten thousands - thousands] [hundreds - tens - units]
since last auto-programming [Hundred thousands - ten thousands - thousands] [hundreds - tens - units]
Code Description
Values (bold = default)
P15 Auxiliary output
0: inactive
1: automatic: gate open indicator light
2: automatic: timed bistable
3: automatic: one-touch
4: controlled: bistable (ON-OFF)
5: controlled: one-touch
6: controlled: timed bistable
P16 Auxiliary output time delay 0 to 60 (time delay value = value x 10 s)
6: 60 s
P17 Lock output
0: active 24V one-touch
1: active 12V one-touch
P18 Lock release
0: inactive - 1: active (Control Box 3S Axovia only)
P19 Closing speed
1: slowest speed at
P20 Opening speed
10: fastest speed
Default value: - Control Box 3s Axovia io: 5
P21 Closing slowdown zone
0: shortest slowdown zone at
P22 Opening slowdown zone
5: longest slowdown zone - Default value: 1
P23 M1/M2 shift when closing 1: minimum shift at
P24 M1/M2 shift when opening
10: maximum shift
Adjusted when auto-programming complete
P25 M1 closing torque
limitation
P26 M1 opening torque
limitation
P27 M1 slowdown torque
limitation when closing
P28 M1 slowdown torque
1: minimum torque at
limitation when opening
10 (Axovia) or 20 (Ixengo): maximum torque
P29 M2 closing torque
Adjusted when auto-programming complete
limitation
P30 M2 opening torque
limitation
P31 M2 slowdown torque
limitation when closing
P32 M2 slowdown torque
limitation when opening
P37 Wired control inputs
0: complete cycle mode - pedestrian cycle
1: opening mode - closing
P39 Limit position maintaining
0: without time delay - 1: with time delay
time delay
(Control Box 3S Ixengo only)
P40 Coupling speed when
1: slowest speed at
closing
4: fastest speed
P41 Coupling speed when
Default value: 2
opening
Programming code display
Code Description
h0
Awaiting setting
hc1
Awaiting setting + 9.6 V power supply
hu1
Awaiting setting + 24 V power supply
h1
Awaiting start of auto-programming
h2
Auto-programming mode - opening
h4
Auto-programming mode - closing
F0
Awaiting remote control memorisation for operation in complete opening mode
F1
Awaiting remote control memorisation for operation in pedestrian opening mode
F2
Awaiting remote control memorisation for remote lighting control
F3
Awaiting remote control memorisation for auxiliary output control
Solution?
Check that "P07" is correctly configured. Check the wiring of the cells.
Check that "P09" is correctly configured. Check the programm. safety input wiring.
Check that no obstacles are causing the cells or safety edge to detect.
Check that "P2" is correctly configured in relation to the device connected to the safety input.
Check the safety device wiring.
Check that the photoelectric cells are correctly aligned.
Check the motor wiring.
Check the wiring, then disconnect the power supply for 10 seconds.
N.B.: maximum accessories consumption = 1.2 A
Repeat an order. If the fault persists, contact Somfy.
N.B.: maximum accessories consumption = 1.2 A
Check the consumption of the connected accessories.
Normal operation (attempted intrusion, current reinjection activated, etc.)
Disconnect the backup battery and connect the control box to the mains to switch it on for
the first time.
- Control Box 3s ixengo io: 6
Setting
compl.

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis