TEMPERATURE COMPENSATED CHARGING
Below -20ºC:
Output voltage fixed 12Volt
From -20ºC until +50ºC
20ºC is reference point (= charge voltage setting)
Voltage compensation of 30mV per ºC
Output voltage is max. 14,8Volt
+50ºC
Above
Output voltage fixed 12Volt
TEMPERATURE COMPENSATED CHARGING
Below 0ºC:
Charge current will be reduced to 10%
55
LEAD ACID BATTERY SETTINGS
LIFEPO4 SETTING
Schedule is an example
at a charge setting of
14,4Volt