Herunterladen Inhalt Inhalt Diese Seite drucken

Victron energy BlueSolar MPPT 150/45-Tr Anleitung Seite 9

Vorschau ausblenden Andere Handbücher für BlueSolar MPPT 150/45-Tr:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 48
3.5 Configuration of the controller
Fully programmable charge algorithm (see the software page on
our website) and eight preprogrammed charge algorithms,
selectable with a rotary switch:
Pos
Suggested battery type
0
Gel Victron long life (OPzV)
Gel exide A600 (OPzV)
Gel MK
Gel Victron deep discharge
Gel Exide A200
1
AGM Victron deep discharge
Stationary tubular plate (OPzS)
Rolls Marine (flooded)
Rolls Solar (flooded)
Default setting
Gel Victron deep discharge
2
Gel Exide A200
AGM Victron deep discharge
Stationary tubular plate (OPzS)
Rolls Marine (flooded)
Rolls Solar (flooded)
3
AGM spiral cell
Stationary tubular plate (OPzS)
Rolls AGM
4
PzS tubular plate traction
batteries or
OPzS batteries
5
PzS tubular plate traction
batteries or
OPzS batteries
6
PzS tubular plate traction
batteries or
OPzS batteries
Lithium Iron Phosphate (LiFePo
7
batteries
Note 1: divide all values by two in case of a 12V system and multiply by two
in case of a 48V system.
Note 2: equalize normally off, see sect. 3.7.1 to activate
Absorption
Float
V
28,2
27,6
28,6
27,6
28,8
27,6
29,4
27,6
29,8
27,6
30,2
27,6
30,6
27,6
)
4
28,4
27,0
Equalize
V
V
@%I
nom
31,8
@8%
32,2
@8%
32,4
@8%
33,0
@8%
33,4
@25%
33,8
@25%
34,2
@25%
n.a.
dV/dT
mV/°C
-32
-32
-32
-32
-32
-32
-32
0
7

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis