Brief description

The A 210 is a panel mounting instrument for monitoring AC systems
with dimensions 96 x 96 mm. The following measurements are
acquired: voltages, currents, frequency, and phase angles in single
phase or 3 phase systems. From these, the active power, reactive
power, apparent power, active energy, reactive energy, and the power
factor and the neutral current can be calculated. With the use of
voltage and current transformers, the instrument can be used for
measurements in medium and high voltage systems. The trans-
formation ratios are configurable for the direct display of all
measurements. The A 210 instrument is used as a display with two
S0 pulse or limit value outputs.

Technical data

Measuring inputs
Nominal frequency:
Nominal input voltage:
Nominal input current:
Continuous thermal ratings of inputs
10 A at 346 V single phase AC system
10 A at 600 V 3 phase system
Short-time thermal rating of inputs
Input
Number
variable
of
inputs
577 V LN
10
100 A
10
100 A
5
Measuring ranges
U, I, S:
P, Q:
F:
cosϕ:
Pulse/Limit value outputs
Depending on the function selected, the two digital outputs can be
used either as pulse outputs for actual and reactive energy or as
limit signals
The outputs are passive, and are galvanically isolated from all the
other circuits by opto-couplers.
External voltage source:
Load current:
Pulse outputs
The values for measured reactive and active energy can be read out
at the pulse outputs in the form of standard S0 pulses for the driving
of electromechanical counting mechanisms (pulse duration
>100 mA).
External voltage source
20
SO2
R
L
21
SO1
22
For systems with external transformers, the pulses are for the primary
energy data.
20
Mod-Tronic Instruments Limited Tel: 1 800 794-5883 Fax: 1 800 830-7122 www.mod-tronic.com
50, 60 Hz
Phase-phase: 500 V
Phase - N: 290 V
5 A or 1 A
Duration
Interval
of
between
overload
two overloads
1 s
100 s
1 s
100 s
1 s
5 min
≤ 120% of nominal value
≤ ± 120% of nominal value
45 to 65 Hz
± 1
8 to 30 V DC
ON = 10 to 27 mA, OFF ≤ 2 mA
U
e.g. energy import
t
U
R
L
e.g. energy export
Power supply*
DC, AC power pack 40 to 400 Hz
85 to 253 V AC/DC or
20 to 70 V AC/DC
Power input:
* For power supplies > 125 V the auxiliary circuit should include an
external fuse.
Accuracy data
Acc. to IEC 688 resp. EN 60 688
0.5% for voltage and current values
1% for power and cosϕ values
0,1% for frequency
Environmental conditions
Operating temperature:
Storage temperature:
Relative humidity:
Nominal range of use
0 to 15 to 30 to 45 °C (usage group II acc. to EN 60 688)

Note of maintenance

No maintenance is required.
Display
The measurement display is 3 digit resp. 4 digit (frequency) and
right justified, with the exception of the energy values which are 8
digits. The left-hand 7-segment display is for the sign or an
abbreviation.
Abbreviations:
maximal value
minimal value
average value
max. average value
minimal value for power factor; the worst out of the 3
values of P1, P2, or P3 is displayed
neutral current
inductive
capacitive
incoming
outgoing
interval active power
interval reactive power
interval apparent power
last interval; t-0
,
... previous interval; t-1, -2, -3, -4
overload, out of range indicator
system value
delta voltage
Energy meter
high tariff
low tariff
Interval 0
Interval 1 Interval 2 Interval 3 Interval 4
Current
time t
t-0
t-1

Commissioning

The multi-functional instrument is made operational by switching
on the power supply. The following appears sequentially on the
display:
1. Segment tests: all the segments of the displays and all the LEDs
are lit for 2 s.
2. Version of the software: e.g.: A 210
3. The 3 line voltages at switching on.
Loss of the power supply
All the values configured remain during a loss of the power supply.
On reconnecting the power supply, the last mode selected is
displayed.
< 4 VA (with interface)
< 3 VA (without interface)
-10 to +55 °C
-25 to +70 °C
< 93%
t-2
t-3
t-4
1.04