Opening The Vent Valve; Aligning The Connections Of The Heating Inflow And Return Flow - Daikin Altherma EHSX04P50D Installations- Und Wartungsanleitung

Integrated solar unit
Vorschau ausblenden Andere Handbücher für Altherma EHSX04P50D:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 67
B
Fig. 4-14
Removing the top thermal insulation
2
As required: Remove the bottom thermal insulation in the fol-
lowing order:
▪ Pull the side insulating element off vertically (item A).
▪ Pull the rear insulating element off vertically (item B).
B
A
Fig. 4-15
Removing the bottom thermal insulation
INFORMATION
The thermal insulation is installed in reverse order.
4.4.6

Opening the vent valve

1
Removing the thermal insulation (see
2
Open the vent valve on the pump by one turn.
Daikin Altherma EHS(X/H)
Daikin Altherma integrated solar unit
008.1444099_00 – 07/2018 – EN
C
A
Chap.
4.4.5).
4
Fig. 4-16
Opening the vent valve
4.4.7
Aligning the connections of the heating
inflow and return flow
CAUTION
When working on the hydraulics, pay attention to the in-
stallation position of the O-rings to avoid damaging them
and causing leaks.
▪ Always place O-rings on the part to be inserted after dis-
assembly or before assembly (see
▪ The heating lines must be connected free of tension via
the plug connectors. Establish a suitable strain relief es-
pecially when connecting with flexible lines (not open to
diffusion!) (see ).
CAUTION
If the plug brackets cannot be put on properly, the coup-
lings can be detached from their mountings to ensure a
very strong or continuous escape of liquid can occur.
▪ Before putting on a plug bracket, make sure that the stir-
rup engages in the coupling groove. To do so, insert the
coupling far enough into the mounting that the groove is
visible through the plug bracket mounting.
▪ Insert the plug bracket up to the end stop.
The connections of the heating inflow and return flow can be direc-
ted upwards or backwards in order to adapt it optimally to the struc-
tural conditions of the installation site.
The device is supplied with upwards aligned connections as stand-
ard. The following conversion steps are required in order to direct
the connections to the rear out of the device:
1
Remove the protective cover and top thermal insulation
(see Chap.
4.4.2).
Set-up and installation
Fig.
4-18).
Installation and maintenance instructions
17