Herunterladen Inhalt Inhalt Diese Seite drucken

Mitsubishi Electric CMB-PW202V-J Installationshandbuch Seite 3

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 11
[Fig. 2.4.2]
●Restrictions on piping length
PURY-P200/250/300YHM-A
PQRY-P200/250/300YHM-A
1000
900
800
700
600
500
400
300
200
10
20
A Total piping length (m)
3
[Fig. 3.2.1]
4
[Fig. 4.1.1]
Unit model
Model name
PURY-(E) P200
(BC CONTROLLER)
PQRY-P200
CMB-PW202V-J
PURY-(E) P250
PQRY-P250
PURY-(E) P300
PQRY-P300
PURY-P350
Indoor unit side
A
C
B
B
C
D
e
d
D
D
A To outdoor unit
B End connection (brazing)
C BC controller
D Indoor unit
E PWFY unit
30
40
50
60
70
80
90
100 110
B
B Piping length between outdoor unit and BC controller (m)
A
B
(Top view)
1
BC CONTROLLER
High pressure
Low pressure
side
side
ø15.88*1
ø19.05*1
(Brazing)
(Brazing)
ø22.2
ø19.05
(Brazing)
(Brazing)
ø28.58*1
(Brazing)
B or C
B or C
(Brazing)
(Brazing)
*1 Use the supplied pipe.
B
E
a
b
E
E
g
f
D
E
2.4
PURY-P350YHM-A, PURY-EP200/250/300YHM-A
1000
900
800
700
600
500
400
300
200
10
20
30
3.2
14
1 Hanging method
A: Min. 30 mm
A Hanging bolt ø10 (field supply)
B Washer (field supply)
4.1
B, C, D, E
Å Total capacity of indoor units
~ 140
141 ~ 200
201 ~ 300
301 ~ 400
401 ~ 650
a, b, c, d, e, f, g
Î Model number
20,25,32,40,50
63,71,80,100,125,140
200
250
‰ Downstream unit model total
~ 200
201 ~ 400
401 ~ 650
c
Ì 4-Branching header
E
(Downstream unit
model total
200)
CMY-Y104-G
40
50
60
70
80
90
100 110
B
ı Liquid pipe
ø9.52
ø9.52
ø9.52
ø12.7
ø15.88
ı Liquid pipe
ø6.35
ø9.52
ø9.52
ø9.52
Ï Joint
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
Ó 8-Branching header
È 10-Branching header
(Downstream unit
(Downstream unit
model total
400)
model total
CMY-Y108-G
CMY-Y1010-G
(mm)
Ç Gas pipe
ø15.88
ø19.05
ø22.2
ø28.58
ø28.58
(mm)
Ç Gas pipe
ø12.7
ø15.88
ø19.05
ø22.2
650)
3

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis