Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection And Operation; Electrical Connection; Start-Up - Phoenix Contact MCR-S-1-5-UI-DCI Betriebsanleitung

Strommessumformer
Vorschau ausblenden Andere Handbücher für MCR-S-1-5-UI-DCI:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 4

4. Electrical connection and operation

4.1. Electrical connection

• When operating this electric measuring transducer, the national regulations (e.g.
Germany VDE 0100 "Conditions for the erection of power installations with nominal
voltages below 1000 volts") must be observed during installation and selection of the
electrical conductors.
The following format applies only for MCR-S-10-50-...:
• The measuring line fed through the module has to feature at least basic insulation.
• Y : A wire voltage of 300 V AC or DC toward earth may not be exceeded on the
measuring line!
• Δ : With three-phase alternating current, a line voltage of 519.6 V may not be exceeded!
Pin configuration:
Connecting
terminal block
1
2
3
4
Terminal blocks 5 - 8 only for MCR-S-1-5-...-DCI:
5
6
7
8
9
0
!
"
§
$
%
&

4.2. Start-up

Before putting this measuring transducer into operation, please ensure that the
configuration data comply with the requirement.
The configuration data for a preconfigured device are to be found on the right hand side of the housing.
When using a non-configured measuring transducer, a standard configuration that can be found in
"7.1. Order key" is set.
Should the desired configuration not match that on the label on the side or the standard configuration,
please observe the following point, "Functional diagram for configuration".
18
Description
only threshold value module: (12) N/C contact
only threshold value module: (11) Center contact
only threshold value module: (14) N/O contact
10 A input
5 A input
1 A input
Ground reference for 1, 5 and 10 A input
Current output
Voltage output
Ground reference for current or voltage output
Ground reference for current or voltage output
Operating voltage (+24 V DC)
Ground reference for operating voltage
only threshold value module: transistor output
only threshold value module: ground reference for transistor output

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis