Herunterladen Inhalt Inhalt Diese Seite drucken

Remote Control; Troubleshooting - STEINEL DUAL HF DALI Handbuch

Vorschau ausblenden Andere Handbücher für DUAL HF DALI:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Parallel-connected Configurations n
When using several detectors, they must be connected to the same phase!
u
Master/master
14
The "P" input provides the capabil-
It is not possible to wire two DALI
ity of extending the zone move-
power supply units through the "P"
ment is detected in.
input as the DALI version only pro-
vides one input for "P". It is only
possible to extend the detection
Burning-in function
Note:
To ensure trouble-free sensor op-
eration, we recommend seasoning
If tubes are not seasoned or ambi-
the tubes by leaving them
ent temperatures are low, the sen-
switched 'on' for 100 hours. This
sor may not switch the light OFF. In
seasoning process can increase
this case, switch the light "OFF"
tube life. This function is activated
and, for the time being, drastically
using the RC 5 remote control..
reduce the reach setting.

Remote Control

Using the remote control (option-
Presence Control remote control
al), functions can be conveniently
unit:
activated from the floor.
User remote control RC 5
EAN No.: 4007841 592806
Service remote control RC 8
EAN No.: 4007841 559410

Troubleshooting

Malfunction
Cause
L No supply voltage
Light does not switch 'ON'
L Lux setting too low
L No motion detection
L Lux setting too high
Light does not switch 'OFF'
L Stay-'ON' time running out
L Interference from sources
of heat, e.g.: fan heater,
open doors and windows,
pets, light bulb/halogen
floodlight, moving objects
(IR Quattro)
zone with a Presence Control PRO
COM1/COM2 or DIM version.
Please only use high-quality
brand-name lamps. Otherwise,
we cannot guarantee that this
high-precision sensor will operate
reliably.
Remedy
L Check supply voltage
L Slowly increase lux setting
until light switches 'ON'
L Ensure unobstructed sensor
vision
L Check detection zone
L Reduce lux setting
L Wait until stay-'ON' time
elapses; reduce stay-'ON'
time if necessary
L Use stickers to mask out
stationary sources of
interference
- 24 -
Malfunction
Cause
L Stay-'ON' time too short
Sensor switches 'OFF' in spite of
L L ight-level threshold too low
persons being present
L Stay-'ON' time too long
Sensor does not switch 'OFF'
quickly enough
L Reach is reduced when
Sensor does not switch 'ON'
quickly enough when
approached from the front
approached from the front
L Lux setting too low
Sensor does not switch 'ON'
when persons are present in
spite of it being dark
L Sensor in semi-automatic
Sensor does not switch 'ON'
selected basic brightness in
mode
L Lux setting too low
spite of it being dark
L Sensor operating at the limit
Other faults
of specific temperature
ranges
Declaration of Guarantee
Making Claims
All rights are based on our guar-
antee period. We guarantee that
If you wish to make a claim,
your STEINEL Professional sensor
please send your product com-
product will remain in perfect
plete and carriage paid with the
condition and proper working
original receipt of purchase,
order for a period of 5 years.
which must show the date of
We guarantee that this product is
purchase and product designa-
free from material, manufactur-
tion, either to your retailer or
ing and design flaws. In addition,
directly to us at STEINEL (UK)
we guarantee that all electronic
Limited, 25 Manasty Road,
components and cables function
Axis Park, Orton Southgate,
in the proper manner and that all
Peterborough, PE2 6UP. For this
materials used and their surfaces
reason, we recommend that you
are without defects.
keep your receipt of purchase in
a safe place until the guarantee
period expires. STEINEL shall
assume no liability for the costs
or risks involved in returning a
product.
Remedy
L Increase stay-'ON' time
L Change light threshold
L Reduce stay-'ON' time
L Install additional sensors
L Reduce distance between
two sensors
L Sensor deactivated by
switch/button?
L Semi-automatic mode?
L I ncrease light-level threshold
L Sensor in fully automatic
mode
L Increase light-level threshold
L See Tech. specs.
For information on making
claims under the terms of the
guarantee, please go to
www.steinel-professional.de/
garantie
If you have a guarantee claim or
would like to ask any question
regarding your product, you are
welcome to call us at any time
on our service hotline
01733 366700.
- 25 -

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis