Functions – Settings by Potentiometer
Potentiometer e
Twilight setting
The chosen response threshold
Control dial turned fully clockwise:
can be infinitely varied from
MAX daylight mode
approx. 10 – 1000 lux.
Control dial turned fully anti-clock-
wise: MIN night-time operation
Examples of Use
Night-time mode
Corridors, foyers
Stairs, escalators, moving walkways
Washrooms, toilets, switchrooms, canteens
Sales floor, kindergartens, nursery school rooms,
sports halls
Work environments: Offices, conference and meet-
ing rooms, precision assembly activities, kitchens
Working areas requiring good light:
Laboratory, technical drawing, precision work
Daylight mode
Note: Depending on the site of installation, the setting may need to be corrected by 1 – 2 marks on the scale.
Brightness is measured directly at the sensor.
Potentiometer f
Time setting
Stay-'ON' time for switching
The chosen stay-'ON' time is
output 1 & 2
infinitely variable from a min-
Setting 30 sec. – 30 min.
imum of approx. 30 sec. to a
maximum of 30 min. Light is
calibrated after 3 min.
IQ mode
Turned fully clockwise:
behaviour. The optimum time
The stay-'ON' time is self-learning
cycle is determined by means
and adjusts dynamically to user
of a learning algorithm.
Potentiometer g
Basic brightness (DIM/DALI version)
Provides basic illumination for the
controller 'OFF') or adjusts to the
selected stay-'ON' time when am-
preselected brightness level
bient light falls below the selected
(constant-lighting controller 'ON').
brightness threshold that is set.
When no movement is being
This can be dimmed to 10% of
detected, the detector dims back
maximum light intensity. As soon
to basic brightness after the stay-
as a person enters the scene, the
'ON' time expires. This is switched
detector switches either to 100%
'OFF' when stay-'ON' time (1 min. –
light intensity (constant-lighting
30 min.) has expired or the day-
Depending on the site of installa-
tion, the setting may need to
be corrected by 1 – 2 marks on
the scale.
Brightness settings
min
1
2
3
4
5
>=6
max
When the threshold is exceeded,
the sensor switches 'OFF' after
the stay-'ON' time expires.
The shortest time is 5 min.,
the longest 20 min.
light component is sufficient to
exceed the selected level of bright-
ness. In the 'ON' setting, the detec-
tor switches basic brightness 'ON'
and 'OFF' as soon as the level of
light falls below the brightness
threshold.
- 24 -
Parallel-connected Configurations n
When using several detectors, they must be connected to the same phase!
u
Master/master
14
The 'P' input provides the capabili-
It is not possible to wire two DALI
ty of extending the zone move-
power supply units through the 'P'
ment is detected in.
input as the DALI version only pro-
vides one input for 'P'. It is only
Burning-in Function
To ensure trouble-free sensor op-
Note:
eration, we recommend seasoning
If tubes are not seasoned or ambi-
the tubes by leaving them switched
ent temperatures are low, the sen-
'ON' for 100 hours. This seasoning
sor may not switch the light 'OFF.'
process can increase tube life. This
In this case, switch the light 'OFF'
function is activated using the RC 5
and, for the time being, drastically

remote control.

reduce the reach setting.
Remote Control
Using the remote control (option-
Presence Control remote control
al), functions can be conveniently
unit:
activated from the floor.

Troubleshooting

Malfunction
Cause
L No supply voltage
Light does not switch 'ON'
L Lux setting too low
L No motion detection
L Lux setting too high
Light does not switch 'OFF'
L Stay-'ON' time running out
L Interference from sources
of heat, e.g.: fan heater,
open doors and windows,
pets, light bulb/halogen
floodlight, moving objects
(IR Quattro)
Sensor switches 'OFF' in spite of
L Stay-'ON' time too short
L L ight-level threshold too low
persons being present
possible to extend the detection
zone with a Presence Control PRO
COM1/COM2 or DIM version.
Please only use high-quality
brand-name lamps. Otherwise,
we cannot guarantee that this
high-precision sensor will operate
reliably.
User remote control RC 5
EAN No.: 4007841 592806
Service remote control RC 8
EAN No.: 4007841 559410
Remedy
L Check supply voltage
L Slowly increase lux setting
until light switches 'ON'
L Ensure unobstructed sensor
vision
L Check detection zone
L Reduce lux setting
L Wait until stay-'ON' time
elapses; reduce stay-'ON'
time if necessary
L Use stickers to mask out
stationary sources of
interference
L Increase stay-'ON' time
L Change light threshold
- 25 -