Risk of injury and damage to
assets!
Check all units and components
for correct connection and
proper function.
11.1 Adjustment
Adjust the output following the
installation of the reed chain and after
the connection to the supply voltage
using an external measuring
instrument.
This is carried out with the two
trimmer potentiometers accessible
from the side.
Compensation between the non-linear
scaling of the flowmeter and the linear
output signal of the flow data sensor
must be performed by adjusting,
preferably between 20 % and 80 % of
the flow rate.
Here 20% corresponds to 7.2mA and
80% to 16.8mA.
Connect the ammeter and the
respective voltage supply to the
flow data sensor
Allow 20% of the flow to pass the
DFM
Set the min. trimmer
potentiometer (3) such that the
corresponding current (7.2mA) is
shown in the ammeter
Allow 80% of the flow to pass the
DFM
Set the max. trimmer
potentiometer (3) such that the
corresponding current (16.8mA)
is shown in the ammeter
Check the values at 20% and
80% several times and repeat
the adjustment, if required
8
12.
Technical data
12.1 Components
1.
Notches for the measuring range
2.
Potentiometer for the upper limit
value of the output signal
3.
Potentiometer for the lower limit value
of the output signal
4.
Plug connector
12.2 Measuring value
• Flow
12.3 Measuring principle
• Reed chain
• Trigger element Magnetic float
12.4 CE sign
• DIN EN 61326-1, DIN EN 55022/B
12.5 Type of protection
• with IP 65 plug
12.6 Voltage supply
• Uin = 18 ... 30 V DC
12.7 Connection cable
• Cable outside diameter: 6 ... 8mm
• Nominal cross-section: max. 0.75
2
mm
Document 330619 – 2014/02/26