Herunterladen Inhalt Inhalt Diese Seite drucken

Rs-485 Interface (Optional); Communication Protocol; Standard Setting; Excerpt From Register Addresses - Pce Instruments Pce-Wsac 50 Bedienungsanleitung

Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

6

RS-485 interface (optional)

The communication with the wind speed alarm controller PCE-WSAC 50 is enabled by the
MODBUS RTU protocol and the serial RS-485 port. This allows different registers containing the
measured wind speed, the wind scale and other information to be read.
6.1

Communication protocol

The registers can be read by means of the Modbus function 03 (03 hex) and written into
by the function 06 (06 hex).
Supported baud rates
Data bits
Parity bit
Stop bits
Data type of registers
6.2

Standard setting

Baud rate
Parity
Stop bit
Address
6.3

Excerpt from register addresses

Register
Register
address (dec)
address (hex)
0000
0000
0001
0001
0034
0022
0035
0023
0080
0050
0081
0051
0084
0054
1200, 2400, 4800, 9600, 14400, 19200,
38400, 56000, 57600, 115200
8
None
1 or 2
16-bit unsigned integer
9600
None
1
123
Description
Current wind speed in m/s
Current wind scale
Pre-alarm
Alarm
Modbus address
Baud rate (12 = 1200 baud, 24 = 2400 baud,
etc.)
Stop bits (1 or 2)
© PCE Instruments
29
R/W
R
R
R/W
R/W
R/W
R/W
R/W
Inhaltsverzeichnis
loading