CAUTION
• Ensure that the space around the left and right of the indoor unit is more than 12cm.
The indoor unit should be installed allowing a minimum clearance of 15cm from the ceiling.
• Use a stud finder to locate studs to prevent unnecessary damage to the wall.
A minimum pipe run of 3 metres is required to minimise vibration & excessive noise.
• The indoor unit should be installed on the wall at a height of 2.3 metres or more from the
floor.
• At least two of the directions A, B and C should be free from obstructions.
ATTENTION
• This illustration is for explanation and indication purposes only. The illustrations may be
different from the airconditioner you purchased.
• Copper lines must be insulated independently from each other.

INDOOR UNIT INSTALLATION

Correct orientation
of Installation Plate
12 cm or more
Air filter
Remote
Controller
Controller
Air outlet
connective cable
Fig. 4
15 cm or more
12 cm or more