Error messages

Display of missing/defective slaves
(digit 2 = master; digits 3 and 4 = slave no.);
the slaves are displayed at intervals of seconds.
The list of failed slaves can be stored until the slaves
have been replaced.
- Press the SET button twice (for the list of master 1)
or SET -MODE - SET (for the list of master 2). The
lowest address of the error list is displayed flashing.
- Replace the failed slave by a slave with the same
configuration and with the address 0; it will receive
the indicated address; (the function "automatic
addressing" must be activated). If other addresses
are displayed, proceed in the same way until the list
has been completed.
- The function will be ended when the slaves have
been replaced or the SET button has been pressed.
Bus error or timeout at field bus interface
Software version AS-i string 1 ≠ AS-i string 2
error during initialisation of the Profibus interface module
AS-i master 2: operating mode already active
AS-i master 2: addressing mode already active
AS-i master 2: error during the setting of the new address
AS-i master 2: error during the deletion of the old address
AS-i master 2: slave with old address does not exist
AS-i master 2: slave with new address exists
AS-i master 2 offline/slave 0 exists