Herunterladen Inhalt Inhalt Diese Seite drucken

Drain Piping Work; Piping And Drain Hose Installation - Toshiba RAV-SM802KRT-E Installationshandbuch

Vorschau ausblenden Andere Handbücher für RAV-SM802KRT-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5

DRAIN PIPING WORK

Piping and drain hose installation

In case of right-side exit
• Cut out the knockout portion by the slits with a knife or pair of wire cutters as necessary.
In case of downward pipe exit
• Cut out the knockout portion by the slits with a knife or pair of wire cutters as necessary.
Piping via left-hand connection
Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid
exceeding 43 mm above the wall surface, the indoor unit could be unstable when set on the wall. When bending the
connecting pipes, always use a suitable bending tool to avoid damaging the pipes.
Bend the connection pipe within a radius of 30 mm.
To connect the pipe after installation of unit (figure)
Outward form of indoor unit
If the pipe is bent incorrectly, the indoor unit could be unstable on the wall.
After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and
insulate as necessary.
Slit (Body right)
Slit (Body right)
400 mm
300 mm
R 30 mm
Use the handle of a screwdriver, etc.
(To the front of the flare)
Liquid side
Gas side
NOTE
6
EN

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Rav-sm562krt-e

Inhaltsverzeichnis