Technical data
The power supply and electrical control systems must only be operated with components that are approved by the manu-
facturer.
LON Modules
Electrical properties
Mains supply voltage:
Power consumption (standby):
Power consumption (max. operation)
Connecting terminal:
Fuse:
Class of protection:
Analog input stages
Sensor voltage supply:
Input resistance:
Input current:
Connecting terminal:
Behaviour if sensor breaks:
Tolerance:
Digital input/output stages (SELV)
Output voltage:
Input voltage:
13424999465
01|
LON Modules Analog 8in, Analog 2out6in, Digital 8in/out, Relay 8out
LON Modules Analog 8in, Analog 2out6in, Digital 8in/out, Relay 8out
Analog 8in
24 V DC [-25%/+50%]
< 1 W
12 W
Spring-loaded connection for wire cross-section
rigid min. 0.2 mm²
rigid max. 1.5 mm²
flexible min. 0.2 mm²
flexible max. 1.5 mm²
flexible with wire end ferrule without plastic casing min. 0.25 mm²
flexible with wire end ferrule without plastic casing min. 1.5 mm²
flexible with wire end ferrule without plastic casing min. 0.25 mm²
flexible with wire end ferrule without plastic casing min. 0.75 mm²
Poly fuse
Class III compliant with VDE 0106, ICE 60536
24 V DC; max. 50 mA/switchable
75 Ω (measuring resistance)
4–30 mA
Refer to connecting terminal, electrical
properties
Here the zero point is 0 mA
< 1% (20 mA) at 20°C
Analog 2out6in
Digital 8in/out
10 W
12 W
24 V DC with 35
mA
12–30 V DC
Relay 8out
3 W
35