LON Analog Module 2out6in
General information
Used for the connection of 6 analog sensors, selectable as two- or three-conductor system. The two additional analog
outputs can be used as a power outlet. The rated level range of the individual sensors is 4–20 mA. The inputs of the LON
Analog Module 2out6in can be provided with 50 mA for each sensor. The inputs and outputs are short-circuit proof.
Connecting options
Outputs
•
Activation of a building control system (BCS) or energy management control system
•
Activation of infinitely variable drives (e.g., solar protection)
Inputs
•
Differential pressure transmitters/pressure sensors
•
Temperature sensors
•
CO
sensors
2
•
Air quality sensors
•
Light intensity sensors
•
Wind force sensor
•
Wind direction sensor
Connection example
LON-Bus
J-Y(ST) Y 2 x 0.8 mm
2 (1)
up to 200 m J-Y(ST) Y 2 x 2 X 0.8 mm
up to 350 m J-Y(ST) Y 4 x 2 X 0.8 mm
The cable type serves only as an example. Compliance with the cabling specifications for LON networks is mandatory.
1)
LON connection of LON modules using an adapter plate
2)
The specified cable cross-sections must not be reduced. They are defined for an ambient temperature of 20° C. If higher
temperatures are applied, the cross-section must be increased. All wires to the LON BOX carry a voltage of 24 V DC and
must be routed separately from the mains supply line. When routing the wiring, compliance with the VDE regulations is
mandatory.
13424999465
01|
LON Modules Analog 8in, Analog 2out6in, Digital 8in/out, Relay 8out
Analog Module 2out6in
2
2
CO
VOC
2
LON Bus
2)
Analog Module 2out6in
lux
Pa
%
LON-Bus
°C
27