Installing the Detector Module
See Figure 3, Page 4:
1.
2.
NOTICE!
Only DM-TP-50(80), DM-TP-10(25) and DM-TP-01(05) detector modules certified to VdS may
be used in the FCS-320-TP1/TP2. Only DM-TT-50(80), DM-TT-10(25) and DM-TT-01(05)
detector modules certified to VdS may be used in the FCS-320-TT1/TT2.The detector module
settings are configured via the DIP switch on the detector module.The sensitivity value is
based on measurements with standard test fires (old value in brackets).
NOTICE!
FCS-320-TP2 and FCS-320-TT2 variants:
These units are factory prepared for the installation of two detector modules:
-
-
-
1.
2.
3.
4.
Setting the Fan Voltage
See Figure 4, Page 5: with jumper JU1, the fan voltage is set on the motherboard. The default
setting is marked in bold.
Fan voltage
6.9 V
9 V
X = pin pair bypassed / O = pin pair open
Number of Detector Modules
See Figure 4, Page 5: The number of populated detector modules is factory set in line with the
model variant (jumper JU4 on the unit's motherboard).
Variant
FCS-320-TP1 / FCS-320-TT1
FCS-320-TP2 / FCS-320-TT2
X = pin pair bypassed / O = pin pair open
Installing the Unit
NOTICE!
-
-
-
-
-
Bosch Sicherheitssysteme GmbH
Open the unit by carefully unlocking the housing cover's quick-release locks with a
screwdriver and then removing the housing cover.
Carefully disconnect the display board connection cable from the motherboard ("DISPL."
connection) and remove the housing cover.
The fan covers for both aspiration pipes are removed.
The two pipe system connections are cut out.
The pin pair on jumper JU4 is open (see Figure 4, Page 5).
Spread the brackets provided for fixing the detector module slightly apart.
Carefully insert the detector module until you hear it click into place. Make sure that the
used detector module is fixed tightly and securely by the bracket by additionally pushing
together the brackets by hand.
Connect detector module 1 to the "HEAD1" connection on the motherboard using the
flatband cable.
FCS-320-TP2 and FCS-320-TT2 variants:
Connect detector module 2 to the "HEAD 2" connection on the motherboard using the
flatband cable.
Reconnect the display board connection cable to the "DISPL." connection on the
motherboard.
When selecting the installation location, ensure that the unit displays are easily visible.
Remember when planning that the unit fans generate a noise level of approx. 45 dB(A).
The air outlet on the unit must not be obstructed. The distance between the air outlet
and adjacent components, e.g. a wall, must be at least 10 cm (4 inches).
The aspirating smoke detector can be installed with the suction device pointing up or
down (to do this, rotate the housing cover through 180°). If the aspiration pipe points
down, make sure no impurities enter the air return pipe, which will be pointing up.
The aspirating smoke detector is either screwed directly to the installation wall by the
rear panel or installed using unit mounting type MT-1, e.g. on frames (see Figure 5,
Page 5: 1 = horizontal installation, 2 = vertical installation).
Jumper JU1, pin no. 1+2
X
O
Number of detector modules Jumper JU4, pin no. 1+2
1 detector module
2 detector modules
en
X
O
F.01U.130.927 | 2.0 | 2010.12