If you select entries NTC, Pt100, Pt1000 or 4-20 mA, when you conclude the configuration process the wizard will
continue configuring the alarms
1- Activate maximum alarm?
4- Activate minimum alarm?
Configuration of input 1 is complete.
The wizard will proceed to the next input, repeating the same steps, until they are all configured.
Upon completion, the logger will automatically begin to record data.
IMPORTANT: If you select NO, all entries will be left with default settings and the unit will begin to
record data. The entries may be re-configured later through the programming menu (see user manual).

Operation

Display modes

There are four possible modes for displaying instantaneous input readings. Press P or O to toggle between the
various modes:
Individual input information
Input
reading
Description
of the input
List of inputs
Description
of the input
Input disabled
Input reading
*
Alarm status
R Alarm activated
T Alarm/event delayed
2- Maximum alarm temperature
5- Minimum alarm temperature
Alarm
status*
( Alarm signal activated
< Maximum alarm / Digital input activation (event)
Sequential input information
Input
reading
Description
of the input
Summary of inputs
(only AKO-15740 and AKO-15742)
Input No.
Probe failure
Input disabled
Input reading
> Alarm signal muted/disabled
= Minimum alarm
20
3- Maximum alarm delay time
6- Minimum alarm delay time