Connecting window motor

Caution: Risk of injury or death from electric shock!
Caution: Risk of injury by crushing hands or fingers!
Attention: 24 V - connection!
Connecting
 A two-core connection cable (cross-section 2 x 0.75
mm²) is required. Lift up skyligt / secure tilt window, con-
nect motor.
Adjusting closing pressure
 Close window 5, retract chain completely and measure
distance X between chain and end coupling 4 and hinge
bracket 3.
 Set limit switch according to value X. One turn of the
key 6 corresponds to one millimetre. + means more con-
tact pressure, - means less contact pressure.
 Estend chain by 10 cm, connect chain end coupling 7
to hinge bracket 3.
Note: If the LED 1 lights up when retracting the
chain (switch off due to overload) the closing pressure
should be re-adjusted.