Mounting On Skylight - STG-BEIKIRCH FM 194-401 RWA Bedienungsanleitung

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Mounting on skylight

Caution: Risk of injury if the windows falls down!
Skylight options
A1
Mounting with coupling plate
A2
Mounting with hinge bracket
Check minimum spacings
P1 = Reference Point!
Chain motor with
194 mm stroke:
A = 400 mm
309 mm stroke:
A = 500 mm
401 mm stroke:
A = 600 mm
B = Supporting surface motor = 75 mm
C= Clearance for hinge bracket = 25 mm
Positioning
 Mark the centre of the casement, mark and drill the
holes for the coupling plate A1 and hinge bracket A2.
Note minimum dimensions requirements!
 Mark centre of frame, mark and drill holes for motor.
Chain motor with
194 mm stroke:
X = 331 mm
309 mm stroke:
X = 423 mm
401 mm stroke:
X = 515 mm
Attaching
 Screw hinge bracket / coupling plate 4 on casement 5.
 Remove end caps 6 from motor and screw on chain
end coupling 7.
 Attach the motor with 4 attachment srews to the win-
dow frame.
07/24999941
SHE chain motor FM 194-401 RWA
A1
P1
A1
A
C
B
A1

37,5 37,5
A2

9
ƒ
4
7
6
...
A2
P1
A2
P1
17
P1
17
9
A1/A2
P1
21
50
X
5
6
17