Mounting on skylight
Caution: Risk of injury if the windows falls down!
Skylight options
A1
Mounting with coupling plate
A2
Mounting with hinge bracket
Check minimum spacings
P1 = Reference Point!
Chain motor with
194 mm stroke:
A = 400 mm
309 mm stroke:
A = 500 mm
401 mm stroke:
A = 600 mm
B = Supporting surface motor = 75 mm
C= Clearance for hinge bracket = 25 mm
Positioning
Mark the centre of the casement, mark and drill the
holes for the coupling plate A1 and hinge bracket A2.
Note minimum dimensions requirements!
Mark centre of frame, mark and drill holes for motor.
Chain motor with
194 mm stroke:
X = 331 mm
309 mm stroke:
X = 423 mm
401 mm stroke:
X = 515 mm
Attaching
Screw hinge bracket / coupling plate 4 on casement 5.
Remove end caps 6 from motor and screw on chain
end coupling 7.
Attach the motor with 4 attachment srews to the win-
dow frame.
07/24999941
SHE chain motor FM 194-401 RWA
A1
P1
A1
A
C
B
A1
37,5 37,5
A2
9
‚
ƒ
4
7
6
„
...
A2
P1
A2
P1
17
P1
17
9
A1/A2
P1
21
50
X
5
6
17