Start-up

Description and settings

Combustion air

1-stage burner
Manual control 103 B
· Loosen the screw on the graduated
segment.
· Select the opening of the air flap
between 0 and 90° from the table as
a function of the power to be
delivered.
· Adjust at the indicated value.
· Tighten the screw on the graduated
segment.
2-stage burner
Servomotor Y10
1
Four red adjustable cams
2
Positioning mark for the cams
relative to the graduated cylinders 4
S
Cam adjusting screw
4
Three fixed cylinders graduated
from 0 to 160°
5
Air flap positioning pointer
6
Plug-in electrical connector
Cam functions
Cam
Function
I
Nominal air flow
II
Air closing on shutdown: 0°
III
Stage 2 fuel-oil valve
energized
· Set between value of the
cam IV and value of the
cam I. In most cases, a
setting just at the half is
suitable.
IV
First stage air flow.
01/2005 - Art. Nr. 13 017 870A
Type
Burner
power
1-stage
kW
80
EK02B.12
100
120
100
EK02B.16
125
160
Burner
power
adjustment
Type
kW
0 to 90°
2-stage
st
d
st
1
st. 2
st.
1
st.
cam IV
70
100
25
EK02B.
90
120
30
16
110
160
35
90
130
30
EK02B.
125
170
40
21
150
210
50
Setting
· Remove the cover.
· Check zeroing of cam drum.
· Pre-set the cams according to the
boiler power and the values shown
in the accompanying table.
m
To do so:
· Actuate the cams using screws S.
The angle position is read in relation
to the index placed on each cam.
Air flap
value
EN
0 to 90°
30
40
50
40
50
70
Cam
d
2
st.
cam I
45
55
70
40
90
90
9