Installation

Fuel-oil connection

Electrical connection

Altitude correction
Pump in suction (H+) or under pressure (H-)
Altitude (m)
H Fictitious (m)
0-500
501-800
801-1300
1301-1800
1801-2200
e.g.: altitude 1100 m. Nominal H = 1 m Actual H 2 m.
Corrected H in suction mode
2 + 1 = 3m
Corrected H in pressure mode 2 - 1 = 1m
Select pipe Ø from table in accordance with
length required between
and pump.If
tank
corrected H in suction mode is above 4 m, include
transfer pump (max. pressure 2 bar)
L (m) of double-tube installation
Corrected
EK02B.12-EK02B.16-EK02B.21
H
Ø (mm
(m)
6/8
4,0
17
3,0
14
2,0
12
1,0
10
+0,5
9
0
8
-0,5
7
-1,0
6
-2,0
4
-3,0
-
6
Fuel oil connection
Enclosed diagrams provide required
pipe diameters.
There are two following possibilities:
Direct suction:
According to length L and suction or
load height H and chance mishaps ;
These lengths include the presence
of a quarter-turn hand-operated
valve, a check valve and four elbows.
Maximum negative pressure 0.4bar.
Transfer loop:
According to the type of facility,
booster pump characteristics will
have to meet several criteria, notably:
– hourly flow,
– fluid flow speed,
– maximum boosting pressure.
Preference should be given to this
type of installation, in order to obtain
long spray pump life.
0
In both cases, it is compulsory to fit a
0.5
120µm filter and quarter-turn
hand-operated valve on the suction or
1.0
booster (not supplied).
1.5
2.0
Important:
Suction:
· Totally fill suction pipe between
spray pump and tank down-pipe with
fuel oil.
Transfer loop:
· Fill, boost, drain and set pressure in
circuit at 2bar max. It is advisable to
install a pressure switch to limit
burner operation to boost pressure.
· Check for possible leaks.
)
8/10
54
47
40
34
31
27
24
21
14
8
Electrical connection
The electrical characteristics such as
voltage, frequency, power, are
mentioned on the identification plate.
Minimum conductor section: 1.5 mm²
Delayed-action minimum protection
device: 6.3 A
Refer to the wiring diagrams for the
electrical connections:
– diagram enclosed with the burner
– diagram screen printed on socket
7 P
– diagram screen printed on socket
4 P in the case of controller
thermostat).
m
It must be possible to isolate the
burner from the network using an
01/2005 - Art. Nr. 13 017 870A
isolator that connects all poles and
complies with the current applicable
standards. The burner and the heat
generator are interconnected by a
7-pole connector. The cables
connected to this connector must
have a diameter between 8.3 mm
and 11 mm.
Optional :
External connection :
of an alarm between S3 and N.
of one (or more) hour meter
between B4 and N to totals the
operating hours, and between B5
and N to count the operating hours
at nominal flow stage (for 2-stage
burners only).