Start-up

Checking and setting
Combustion components, secondary air

Setting nozzles

B
C
D
E
B
C
4
8
EK02B.12/16
EK02B.21
5
3
1-stage
Burner
power
burners
kW
80
EK02B.12
100
120
100
EK02B.16
125
160
On delivery, the pump is set at 11bar ± 0,5bar.
In bold type: equipment on delivery 1kg fuel à 10°C = 11,86kW
Equivalent nozzles: Danfoss 45°S - Steinen 60°SS, 45°SS - Hago 60P, 45P
Burner
2-stage
power
kW
st
d
burners
1
st.
2
st.
70
100
EK02B.16
90
120
110
160
90
130
125
170
EK02B.21
150
210
On delivery, the pump is set at 11bar ± 0,5bar.
In bold type: equipment on delivery 1kg fuel à 10°C = 11,86kW
Equivalent nozzles: Danfoss 45°S - Steinen 60°SS, 45°SS - Hago 60P, 45P
8
Checking and setting the
combustion components
The nozzles are fitted on delivery.
· Withdraw cell from its seating.
· Disconnect the ignition cables from
the transformer and the oil tube.
· Unscrew (by two rotations) the three
screws from the cover.
· Turn (bayonet system) to withdraw
combustion components.
· Check the ignition electrode settings.
· Adjust and fit the nozzle in
accordance with the boiler power.
D
E
· Reassemble.
1
1
· Check subsequently for leaks.
5
3
Secondary air
This is the flow of air admitted between
the turbulator diameter and the blast tube.
The position of the turbulator
(dimension Y) can be read from the
scale graduated from 0 to 35mm.
Maximum secondary air is indicated by
the 35 mark and minimum secondary
air by 0.
It can be adjusted according to:
ignition quality (shock, vibration,
chatter, delay),
combustion efficiency.
Fuel-oil
Nozzle 45° (1)
flow
US gal/h
kg/h
at 11 bar
6.7
1.75
8.4
2.25
10.1
2.75
8.4
2.25
10.5
2.75
13.5
3.50
Fuel-oil
Nozzle 45° (1)
US gal/h
flow
kg/h
11 - 22 bar
st
d
1
st.
2
st.
5.9
8.4
1.50
7.6
10.1
2.00
9.3
13.5
2.50
7.6
11
2.00
10.5
14.3
2.75
12.6
17.7
3.50
(1) Danfoss S
01/2005 - Art. Nr. 13 017 870A
Dimension
Air adjustment
Y
air flap
mm
0 à 90°
20
30
25
40
35
50
20
40
25
50
35
70
Dimension
Air adjustment
in °
Y
cam IV
cam I
st
d
mm
1
st.
2
st.
10
25
45
20
30
55
30
35
70
15
30
40
20
40
90
35
50
90
Should the blast tube be taken off:
· Upon reassembly, check that fuel
discharge hole is in the lower
vertical position during shut-down.
Setting
This is done without disassembling the
burner (while in operation or when
stopped), in accordance with the values
shown in the accompanying table.
If dimension Y is reduced, CO
increases, and conversely.
· Turn screw A in the direction desired.
2