Herunterladen Inhalt Inhalt Diese Seite drucken

Cascade Without Control Unit; Cascade With Control Unit; Specification; Dimensioned Drawing - STIEBEL ELTRON SOM WMZ SOL Bedienung Und Installation

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

installation

specification

12.3 cascade without control unit
In cascade mode, every heating circuit must have a volumeter
installed. The data calculated can be read centrally via a
datalogger or PC.
configuration / setting:
SOM WMZ SOL "0"
— Master PCB installed in the first SOM WMZ SOL
— Subaddress = "0"
— BUS mode = "cascading"
— BUS master = "Yes"
SOM WMZ SOL "1" to "15"
— Slave PCB installed in the following SOM WMZ SOL
— Subaddress = "1" to "15"
— BUS mode = "cascading"
Any order at the VBUS
®
connection is possible.
Cascade operation without a controller, with PC
12.4 cascade with control unit
A heat meter cascade can be connected directly to a control unit.
The data calculated can be scanned at every heat meter or centrally
via the control unit. An additional PC can be connected.
configuration / setting:
Control unit
— Do not make any adjustments at the control unit. The heat meter
must not be logged on at the control unit.
SOM WMZ SOL "0"
— Slave PCB installed
— Subaddress = "0"
— BUS mode = "cascading"
— BUS master = "No"
SOM WMZ SOL "1" to "15"
— Slave PCB installed
— Subaddress = "1" to "15"
— BUS mode = "cascading"
Any order at the VBUS
connection is possible.
®
Cascade operation with a control unit, and PC
www.stiebel-eltron.com
13. Specification
13.1 Dimensioned drawing
Dimensions
66
104
49
13.2 Specification
model
Type
Part number
specification
Casing
Protection rating
Ambient temperature range
Installation
Displays
Supply
Power consumption approx. VA
setting ranges
Volume ratio, glycol
Pulse rate V 40
Max. flow rate VM 40
Temperature capture
Accuracy
Measuring range
Data BUS system
dimensions and weights
Dimensions H x W x D
Weight approx. kg
VBUS
is a registered trademark of Siemens AG.
®
110
Heat meter
SOM WMZ SOL
PC-ABS and PMMA
IP 20 / DIN 40050
°C
Wall mounting,
optional control panel installation
Graphic LCD,
two-coloured control LED
V
220 ... 240, 50-60 Hz
%
20 ... 70, in steps of 1%
l/Imp
0.1 - 99.9 in steps of 0.1 l/imp
m
/h
3
type
PT1000 sensor
± K
°C
-30 ... + 150
mm
173 x 110 x 46
som Wmz sol |
227729
0 ... 40
2
1.5
0.3
VBUS
®
0.4
27

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis