Herunterladen Inhalt Inhalt Diese Seite drucken

Reset; Language; What To Do If; Led Flashing Codes At The Heat Meter - STIEBEL ELTRON SOM WMZ SOL Bedienung Und Installation

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

operation

WHat to do if...

6.13 reset

Activating this function resets the captured heat volume to zero.
Reset
Adjust. values
Subaddress
Bus mode
Reset

6.14 language

This parameter enables a change of the language of the plain
text display.
adjustment options:
— German
— English
— French
Language
Adjust. values
Sensor 1
Sensor 2
Language
7. What to do if...
If the heat meter does not function correctly, check the following
points.
7.1 leD flashing codes at the heat meter
— Continuous green:
Everything OK
— Red flashing:
At least one sensor is faulty

7.2 Fuses

»
Check the device power supply.
»
Check the fuse on the device PCB.
Fuse
D-37603 Holzminden
SOM WMZ SOL 227729
S1
S2
V40
VBus
1
2
3
4
5
6
9 10
1
Fuse 0.8A (slow)
22
|som Wmz sol
0
Cascaded
0,0 K
0,0 K
English
1
T0,8A
Netz / Mains
220 ... 240 V~
50-60 Hz
IP 20
N
L
12
13
14
19
20
LED flashes red.
Sensor faulty. An error code is displayed
in the appropriate sensor display channel
instead of a temperature.
888.8
Lead broken.
Check lead.
Disconnected PT1000 temperature sensors
can be checked using a resistance meter,
and the resistance readings are as below
for the corresponding temperatures.
°c
-10
961
-5
980
0
1000
5
1019
10
1039
15
1058
20
1078
25
1097
30
1117
35
1136
40
1155
45
1175
50
1194
Resistance values of
PT1000 sensors
LED is permanently off.
When the LED is extinguished, check the
controller power supply.
no
The controller fuse has blown. This is
accessible once the cover is removed and
can then be replaced (a spare fuse can be
found in the accessories bag).
- 88.8
Short circuit.
Check lead.
°c
55
1213
60
1232
65
1252
70
1271
75
1290
80
1309
85
1328
90
1347
95
1366
100
1385
105
1404
110
1423
115
1442
OK
www.stiebel-eltron.com

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis