6.6 output

The current output in kW is shown on the top right of the
display.
The accuracy of the output data is subject to the volumeter used.
At low flow rates, deviations from the actual value are possible
for technical reasons.
Output
VL
RL
6.7 Frost protection
Solar heating systems are generally filled with a heat transfer
medium since, on the one hand, temperatures > 100 °C can occur
in the solar circuit, and on the other hand to prevent frost damage
to the system in winter.
6.7.1 Setting
Various heat transfer media are available.
Setting options:
— Water
— Ethylene
— H-30L (factory setting)
— H-30LS
Type of frost protection
Adjust. values:
back
Antifr. type
Volume/Imp.
If glycol or a water/glycol mixtures are used as heat transfer
medium, observe the following information.
6.7.2 H-30L
The anti-freeze is premixed with a mixing ratio of 45% by vol.
6.7.3 H-30LS
The antifreeze is premixed with a mixing ratio of 42% by vol.
6.7.4 Determining the water/glycol ratio
Since the thermal capacity of the heat transfer medium is subject
to the glycol content, first determine the glycol:water ratio.
20
|som Wmz sol
9.30 kW
Power
85,6 °C
45,7 °C
Water
10,0 L/I
The value in % by vol. can be calculated if the volumes of water
and glycol used in the system are known.
% by vol. = (VG : (VW + VG)) x 100
VG:
Volume of glycol
VW:
Volume of water
example:
If there are 15 l water and 20 l glycol in the circuit, the result is:
% by vol. = (20 : (15 + 20)) x 100) = 57
6.7.5 Antifreeze content
The parameter "
Antifreeze cont.
selected in advance as the type of antifreeze.
adjustment options:
Setting range
20% ... 70% by vol.
Factory setting
45%
Antifreeze content
Adjust. values:
back
Antifr. type
Antifreeze
6.8 Pulse value
This adjustable parameter is subject to the volumeter connected.
Note the unit "l/imp" next to the arrow on the volumeter.
If the volumeter V40 provided is used, the pulse value must be set
to 10.0 litres/impulse.
Setting range
0.1 ... 99.9 l/imp
Pulse quality rating
Adjust. values
back
Antifr. type
Volume/Imp.
" is only visible if "
ETHYLENE
Ethylene
45 %
Water
10,0 L/I