Installation
Damage to the actuator by short circuit or corrosion!
Moisture and/or dirt in the actuator.
Make sure that no water enters the actuator.
Mount the cable routing, so it does not point upwards.
Requirements
Wire gauge max. 1.5 mm²
Wire gauge min. 0.75 mm
Sizing of the fuse (customer side): > 6 A
1. Connect the unit plug for the power supply and the unit plug for position feedback
according to wiring diagram, see Chapter 5.4 "Wiring diagram EA15". Make sure that
the cable routing does not point upwards.
Premature component wear due to faulty control!
If the voltage is removed when reaching the end position, the power supply will
discharge the capacitors. Upon startup a higher current can be observed (switching
current) This may cause premature relay wear.
During normal operation avoid switching off the control power to the actuator.
E.g. connect the inputs OPEN/CLOSE as a changeover contact
2. If necessary, adjust the end positions; see Chapter 9.2 "Adjusting end positions".
3. If necessary, adjust the heating element; see Chapter 9.4 "Adjusting the heating
element".
Upon delivery, the heating element is set as follows:
T < 0 °C (< 32°F) heating element is heating
T > 5 °C (> 41°F) heating element switches off again
If required, the switch-on threshold can be set up to 40 °C (104°F).