Start of operation (battery)
1.
Screw on electronic module.
2.
Open shut-off valve.
3.
Connect 9 V alkaline battery (pay attention to correct polarity).
4.
Adjust flushing time
Save water! Adjust fushing time according to flow pressure and flushing quantity.
(1 - 15 s adjustable / 5 s pre-adjusted).
5.
As function control after start of operation the red led is shining for 1 min at user
recognition.
6.
Mount front plate - make function test.
7./8. Adjust active range
9.
Fix front plate.
Diagram – fl ushing quantities
Pressure
1 bar
2 bar
3 bar
4 bar
5 bar
PROOF U8
if necessary.
if necessary (30 - 70 cm adjustable / 50 cm pre-adjusted)
2,0
5,5 s
4,5 s
3,0 s
2,5 s
2,5 s
Flush volume in liters
3,0
7,0 s
10,0 s
5,5 s
4,5 s
4,0 s
4,0 s
Urinal control
SanTec OCEAN U8
EN
4,0
7,5 s
6,0 s
5,5 s
5,0 s