9 SERVICE CALL
PHONE NO. ***************
MOBILE NO. ******************
CONFIRM
ADJUST
The number displayed on the user interface is the phone
number of your local dealer.
10.5.10 RESTORE FACTORY SETTINGS
The RESTORE FACTORY SETTING is used to restore
all the parameters set in the user interface to the factory
setting.
Go to
> FOR SERVICEMAN > 10.RESTORE
FACTORY SETTINGS. Press
be displayed:
10 RESTORE FACTORY SETTINGS
All the settings will come back to
factory default.
Do you want to restore factory
settings?
NO
CONFIRM
Press
to scroll the cursor to YES and press
following page will be displayed:
10 RESTORE FACTORY SETTINGS
Please wait...
5%
After a few seconds, all the parameters set in the user
interface will be restored to factory settings.
10.5.11 TEST RUN
TEST RUN is used to check correct operation of the
valves, air purge, circulation pump operation, cooling,
heating and domestic water heating.
Go to
> FOR SERVICEMAN> 11.TEST RUN.
Press
. The following page will be displayed:
11 TEST RUN
Active the settings and
active the "TEST RUN"?
NO
CONFIRM
. The following page will
YES
. The
YES
If YES is selected, the following pages will be displayed:
11 TEST RUN
11.1 POINT CHECK
11.2 AIR PURGE
11.3 CIRCULATED PUMP RUNNING
11.4 COOL MODE RUNNING
11.5 HEAT MODE RUNNING
ENTER
11 TEST RUN
11.6 DHW MODE RUNNING
ENTER
If POINT CHECK is selected, the following pages will be
displayed:
11 TEST RUN
3WAY-VALVE 1
3WAY-VALVE 2
PUMP_I
PUMP_O
PUMP_C
ON/OFF
11 TEST RUN
PUMPSOLAR
PUMPDHW
INNER BACKUP HEATER
TANK HEATER
3-WAY VALVE 3
ON/OFF
Press ▼ ▲ to scroll to the components you want to check
and press
. For example, when 3-way valve is selected
and
is pressed, if the 3-way valve is open/close, then
the operation of 3-way valve is normal, and so are other
components.
Before the point check, make sure the tank and
the water system is filled with water, and air is
expelled, or it may cause the pump or backup
heater burn out.
If you select AIR PURGE and
page will be displayed :
11 TEST RUN
Test run is on.
Air purge is on.
CONFIRM
56
1/2
OFF
OFF
OFF
OFF
OFF
2/2
OFF
OFF
OFF
OFF
OFF
CAUTION
is pressed, the following
Inhaltsverzeichnis