PMINT—PROFIBUS DP translator
module—installation and use
Table 11. Cyclic Data Exchange Monitoring Format 4
Byte(s)
Data Type
Description
0
Unsigned8
State 0 (byte 0 of monitoring Format 0, Table 7)
1
Unsigned8
State 1 (byte 1 of monitoring Format 0, Table 7)
3–2
Unsigned16
I
(Phase A current)
L1
5–4
Unsigned16
I
(Phase B current)
L2
7–6
Unsigned16
I
(Phase C current)
L3
9–8
Unsigned16
I
(maximum value of I
L max
11–10
Unsigned16
I
(neutral current)
N
13–12
Unsigned16
V
(V
L1-L2
AB
15–14
Unsigned16
V
(V
L2-L3
BC
17–16
Unsigned16
V
(V
L3-L1
CA
19–18
Unsigned16
V
(V
L1-N
AN
21–20
Unsigned16
V
(V
L2-N
BN
23–22
Unsigned16
V
(V
L3-N
CN
25–24
Integer16
cos phi
avg
29–26
Unsigned32
Energy
31–30
Unsigned16
S
(total apparent power)
total
Section 8: PROFIBUS DP-V0 diagnostics
Until the PMINT is parameterized and configured by the PROFIBUS
master, a request for diagnostics by the master will result in
the PMINT returning only the mandatory 6-byte PROFIBUS
diagnostics information .
Once successfully parameterized and configured, the PMINT will
append additional device-related diagnostics information to the
mandatory PROFIBUS diagnostics information, as described in
Table 12 . The diagnostics user data, starting at bit 24, is also
described in the GSD file (Appendix A) .
N
otee:
Configuration is required before this additional information can be
included because the user-defined "Data Object X invalid" bits are defined
by and dependent upon the cyclic data exchange monitoring format selected .
Any change in the PMINT diagnostic information is signaled to the PROFIBUS
master when the PMINT returns a high priority cyclic data exchange .
, I
, I
)
L1
L2
L3
line-to-line voltage)
line-to-line voltage)
line-to-line voltage)
line-to-neutral voltage)
line-to-neutral voltage)
line-to-neutral voltage)
(average of apparent power factor)
Table 12. DP-V0 Unit Diagnostics Definitions
Resolution
Byte
Bit(s)
7
8
7–0
Amps
9
15–8
Amps
10
23–16
Amps
11
24
Amps
25
Amps
26
Volts
27
Volts
28
Volts
29
Volts
30
Volts
31
Volts
0–1000
12
32
kWh
33
kVA
34
35
36
37
38
39
13
40
41
42
43
44
45
46
47
14
48
49
50
51
52
53
EATON CORPORATION www.moeller.net/en/support
04/10 AWB1230-1621
Value
Description
08H
Header: device related diagnostics, length (8 bytes)
81H
Type (status message)
00H
Slot
00H
Specifier
1
No communications with trip unit
1
Data Object 1 invalid (Monitoring Formats 1-4: I
1
Data Object 2 invalid (Monitoring Formats 1-4: I
1
Data Object 3 invalid (Monitoring Formats 1-4: I
1
Data Object 4 invalid (Monitoring Formats 1-4: I
1
Data Object 5 invalid (Monitoring Formats 2-4: I
1
Data Object 6 invalid (Monitoring Formats 2: V
(Monitoring Formats 3-4: V
L1-L2
1
Data Object 7 invalid (Monitoring Formats 2: cos phi
(Monitoring Formats 3-4: V
L2-L3
1
Data Object 8 invalid (Monitoring Formats 2: Energy)
(Monitoring Formats 3-4: V
L3-L1
1
Data Object 9 invalid (Monitoring Formats 3-4: V
1
Data Object 10 invalid (Monitoring Formats 3-4: V
1
Data Object 11 invalid (Monitoring Formats 3-4: V
1
Data Object 12 invalid (Monitoring Formats 3-4: cos phi
1
Data Object 13 invalid (Monitoring Formats 3-4: Energy)
1
Data Object 14 invalid (Monitoring Formats 3-4: S
1
Remote open/closed not enabled (i.e., remote enable switch
disabled, see Section 5)
1
EEROM error alarm (primary status: alarm, cause: 43)
1
RAM error alarm (primary status: alarm, cause: 39)
1
Setpoints error alarm (primary status: alarm, cause: 77)
1
Watchdog alarm (primary status: alarm, cause: 4)
1
Check aux. switch alarm (primary status: alarm, cause: 148)
1
Breaker mechanism fault (primary status: alarm, cause: 154)
1
Breaker shunt trip problem (primary status: alarm, cause: 157)
1
Operations count alarm (primary status: alarm, cause: 31)
1
Earth fault alarm (primary status: alarm, cause: 84, 85)
1
Low power factor alarm (primary status: alarm, cause: 19)
1
Total harmonic distortion alarm (primary status: alarm, cause: 30)
1
Frequency out of bounds alarm (primary status: alarm, cause: 146)
1
Historic trip occurred (primary status: closed, cause: 82)
1
Breaker in Maintenance Mode (cause: 47, 153)
Effective April 2010
)
L1
)
L2
)
L3
)
L max
)
N
)
LL avg
)
)
avg
)
)
)
L1-N
)
L2-N
)
L3-N
)
avg
)
total