PMINT—PROFIBUS DP translator
module—installation and use
Remote enable switch (SW1-1)
The PMINT provides a REMOTE ENABLE switch (see Figure 2)
that will enable/disable access by a PROFIBUS master to control
the opening/closing of the circuit breaker by communications . Refer
to Table 5 .
Table 5. Remote Enable Switch
SW1-1
Remote disable
Open
Remote enable
Close
Reserved switches (SW1-2 and SW1-3)
Switches SW1-2 and SW1-3 on the PMINT are reserved for
future use .
Section 6: PROFIBUS DP GSD file
The current GSD file for the PMINT is listed in Appendix A .
PROFIBUS DP-V0 cyclic data transfers are supported .
Section 7: PROFIBUS DP-V0 profiles
The PMINT supports the PROFIBUS DP profile for low voltage
switchgear devices (LVSG): Circuit Breaker Device Classification .
This classification provides cyclic data exchange structures for
one command (outputs from the PROFIBUS master to the PMINT
slave device) format (Format 0) and four monitoring (inputs from
the PMINT slave device to the PROFIBUS master) formats (Format
0–Format 3) . The PMINT also supports an added monitoring format
(Format 4), similar to Format 3, except the active energy value is
provided with a higher resolution .
SW1-2
SW1-3
X
X
X
X
Cyclic data exchange command structure format
Command structure Format 0 for cyclic data exchange from the
PROFIBUS master supported by the PMINT is described in Table 6 .
The bits are defined as bit 0 is bit 0 of byte 0; bit 8 is bit 0 of byte 1 .
Cyclic data exchange monitoring structure formats
Monitoring structure Formats 0–4 for cyclic data exchange returned
from the PMINT to the PROFIBUS master are described in Table 7
through Table 11, respectively .
The state information bytes are required in all monitoring formats .
The bits are defined as bit 0 is bit 0 of state byte 0; bit 8 is bit 0
of state byte 1 . The definitions are deciphered from the Primary/
Secondary/Cause-Of-Status information reported from the Trip Unit
(see Table 13, Table 14, and Table 15, respectively) .
The multi-byte measurement values of Formats 1–4 are transmitted
most significant byte first, as required by the PROFIBUS protocol .
Table 6. Cyclic Data Exchange Command Format 0
Byte
Bit(s)
Description
0
1–0
Circuit breaker:
00 = no change
01 = switch OFF
10 = switch ON
11 = no change
2
Clear last trip
3
Output 0
4
Output 1
5
Output 2
6
Output 3
7
Output 4
1
9–8
Test mode:
00 = no test
01 = w/o release
10 = with release
11 = with warning
10
Delete history
memory
11
Reset min./max.
memory
12
Reset temperature
min./max. memory
13
Output 5
14
Reset maintenance
information
15
Clock synchronization
EATON CORPORATION www.moeller.net/en/support
04/10 AWB1230-1621
Effective April 2010
Implementation
Open breaker (if remote enabled, see Section 5)
Close breaker (if remote enabled, see Section 5)
"Reset Trip" issued to trip unit
Not implemented
Not implemented
Not implemented
Not implemented
Not implemented
No trip phase current self-test at 3.0 per unit
issued to Digitrip 1150 trip unit only
Not implemented
Not implemented
Not implemented
"Reset all min./max. values" issued to trip unit
Not implemented
Not implemented
"Reset trip unit health buffer" issued to trip unit
Not implemented
5