The use of smoke alarm devices is gov-
erned by DIN 14676.
Minimum equipment
Bedrooms
Children's bedroom
Guest room
Corridors that serve as escape routes
Stairwells of apartment buildings
Optimal equipment
All residential and hobby rooms
Heating and work spaces
Office or workroom
Cellar
Attic
Conditional equipment
In kitchens, smoke alarm devices must
only be installed when false alarms
(e.g., caused by steam) are excluded
Not recommended
Bathrooms are excluded from the in-
stallation of smoke alarm devices due
to the high development of steam
42
Operating Manual: RWM200 - Smoke Alarm Device
Exception: bathrooms with
washing machines and cabinets
4.1 Area to be monitored
Use a device if at least one of the follow-
ing applies:
Monitoring area less than 60 m
and ceiling height of less than 6 m
Ceiling panels (height lower than
20 cm) with joists (ceiling surface
less than 36 m
Use additional equipment if at least one
of the following applies:
Monitoring area greater than 60 m
Ceiling height greater than 6 m
High partial walls
Separating pieces of furniture
Platform / gallery (area greater than
16 m², at least 2 m long and wide)
Ceiling panels (height greater than
20 cm) with joists (ceiling surface
more than 36 m
,
2
)
2
)
2
2
EN