Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection - IFM Electronic EFECTOR 500 Bedienungsanleitung

Elektronischer drucksensor
Vorschau ausblenden Andere Handbücher für EFECTOR 500:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Electrical connection

The unit must be connected by a suitably qualified electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
The device shall be supplied from an isolating transformer having a
secondary Listed fuse rated as noted in the following table.
Control-circuit wire size
AWG
26
24
22
20
18
16
The device shall be connected only by using any R/C (CYJV2) cord,
having suitable ratings.
Disconnect power before connecting the unit as follows:
2 x p-switching
1
2
4
2: OUT2
3
4: OUT1
Connector view (sensor)
Overcurrent protection
2
(mm
)
(0.13)
(0.20)
(0.32)
(0.52)
(0.82)
(1.3 )
BN
L +
WH
BK
BU
L
Maximum protective device rating
Ampere
1
2
3
5
7
10
2 x n-switching
1
2
4
2: OUT2
3
4: OUT1
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white),
3 = BU (blue), 4 = BK (black).
Pin 4 (OUT1) = switching output
Pin 2 (OUT2) = switching output if
OU2 = Hno, Hnc, Fno, Fnc
Pin 2 (OUT2) = diagnostic output if
OU2 = dESI
BN
L +
WH
BK
BU
L
19