Herunterladen Inhalt Inhalt Diese Seite drucken

Ccc-Data Rn 5883; Standard Type; Variants; Ul-Daten Nd 5015 - Dold Varimeter Rcm Datenblatt Und Betriebsanleitung

Differenzstromwächter, allstromsensitiv rn 5883
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

CCC-Data RN 5883

Insulation coordination
according to IEC 60664-1:
RN 5883 cennected with
current transformer ND 5015, ND 5018
Rated impuls voltage /
pollution degree:
Auxiliary voltage / Meas. circuit: 4 kV / 2
Auxiliary voltage / Contacts:
Auxiliary voltage / Analoge output: 4 kV / 2
Contacts / Analoge output:
Meas. circuit / Analoge output: 4 kV / 2
Contacts 11,12,14 / 21, 22, 24: 4 kV / 2

Standard Type

RN 5883.12/61 AC/DC 80 ... 230 V 50 / 60 Hz
Article number:
• For residual current transformer ND 5015/024 and ND 5018/035
• Alarm und Pre-alarm
• Energized or de-energized on trip
• Without analogue output
• Auxiliary voltage U
:
H
• Width:
ND 5015/035/61
Article number:
• Residual current transformer for RN 5883
• Diameter:

Variants

Ordering example for variants
RN 5883 .12 /_ _ _ /61 AC/DC 80 ... 230 V 50 / 60 Hz
For residual current transformer ND 5015/024 und ND 5015/035:
RN 5883.12/001/61:
RN 5883.12/800/61:
RN 5883.12/802/61:
RN 5883.12/004:
For residual current transformer ND 5015/070:
RN 5883.12/011/61:
For residual current transformer ND 5018/105, ND 5018/140,
ND 5018/210:
RN 5883.12/021:
UL-Data ND 5015
Wire connection:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo
4 kV / 2
4 kV / 2
0066451
AC/DC 80 ... 230 V
52.5 mm
0066841
35 mm
Nominal frequency
Auxiliary voltage
UL approval
Variant, if required
Contacts
Type
With analogue output 0 ... 10 V
Fixed values, without analogue output
Fixed values, without analogue output;
with bridge on X1/X2:
- Alarm: Energized on trip
- Pre-alarm: De-energized on trip
Without bridge:
- Alarm: De-energized on trip
- Pre-alarm: Energized on trip
Pre-alarm message and
Alarm message not storing,
reset time 2 s
With analogue output 0 ... 10 V
With analogue output 0 ... 10 V
AWG 24 - 16
60°C / 75°C copper conductors only

Accessories

Residual Current Transformer ND 5015/024, ND 5015/035
C
k
For DIN rail mounting or screw mounting
ND 5015/024
øD
L
Dimensions/mm
24
82
Weight / g
ND 5015/035
øD
L
Dimensions/mm
35
88
Weight / g
Drill tolerance for screw mounting: ± 0.5 mm
*
)

Technical Data Residual Current Transformer ND 5015, ND 5018

Ambient temperature:
Inflammability class:
Insulation coordination according to IEC 61869-1
Highest rated operating voltage U
Rated impulse voltage:
Length of connection wires
Type of wire to CT, e.g.
Single wire:
Single wire twisted pair (pair 1: i1 - k1; pair 2: i2 - k2):
Screened wire; screen one end grounded at device to PE:
Wire cross section:
Stripping length:
ND 5015:
Wire fixing:
Actuation power:
DIN rail mounting:
Screw fixing:
Fixing torque:
ND 5018:
Wire fixing:
Flat terminals with self-lifting clamping piece
DIN rail mounting:
Screw fastening:
(only at ND 5018/105, ND 5018/140, ND 5018/210) M 5
20
D
B
M10979_b
L1
B
H
C
E
F
75
24
54
25
42*
46
Approx. 80
L1
B
H
C
E
F
81
24
67
25
42*
46
Approx. 90
- 40 ... + 60 °C / 233 K ... 333 K
V0 according to UL94
:
m
Up to 10 m
Up to 25 m
0.2 ... 1.5 mm
Terminals with spring connection and
direct (Push in) technology
Integrated clips for vertical and
horizontal mounting
Max. 0.8 Nm
Using mounting adapter ET 5018
RN 5883 / 13.11.25 en / 027B
k
4.2
k
4.2
AC 720 V
3 kV
Up to 1 m
2
8 mm
40 N max.
M3 or M4
Inhaltsverzeichnis