Herunterladen Inhalt Inhalt Diese Seite drucken

Error/Device " Register - Cs Instruments Fa 5 Serie Installation Und Betriebsanleitung

Modbus
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

7.3

"Error/Device " Register

Modbus
Modbus
Register
Address
1101
1100
1103
1102
FA 5xx Modbus RTU Installation
No.of
Data
Description
Byte
Type
Error /
4
Float
Device State
RunTime
4
Float
Counter
Default
Read
Setting
Write
R
R
V1.03
Unit /Comment
Bit 0: Sensor not Calibrated
Bit 1: Low Voltage
Bit 2: Internal Error
Bit 3: Humidity Sensor defect
Bit 4: Humdity out of range
Bit 5: Temperature Sensor defect
Bit 6: Temperature out of range
Bit 7: Calibration recommended
Bit 8: Low Voltage on 4-20mA Option
Bit 9: Pressure Sensor defect
(Option)
This counter records the total
operating time of the device in
seconds, incrementing continuously
while the device is powered and
functioning.