WDT CPR Touch Bedienungsanleitung Seite 17

Modbus tcp kommunikation sps

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Read – Beispiel
3.1.1
Read Coils ( Start Address= 4, Number of States = 1 )
TX
00
00
00
RX
00
00
00
Read Holding Registers ( Start Address = 36, Number of Register = 2 )
TX
00
00
00
RX
00
00
00
Read Discrete Inputs ( Start Address = 67, Number of States = 6 )
TX
00
00
00
RX
00
00
00
Read Input Registers ( Start Address = 10, Number of Registers = 26 )
TX
00
00
00
RX
00
00
00
30.08.2016
num
bytes
00
00
06
FF
00
00
04
FF
num
bytes
00
00
06
FF
00
00
04
FF
num
bytes
00
00
06
FF
00
00
04
FF
num
bytes
00
00
06
FF
00
00
04
FF
function-
Start Register
Number of States
code
01
00
04
00
01
01
01
Num.
State
of
= 1
Data-
bytes
= 1
function-
Start Register
Number of Reg.
code
03
00
24
00
03
04
40
E0
Num.
0x40E0 (Float AB)
of
= 16608
Data-
0x40E00000 (Float AB CD)
bytes
= 4
function-
Start Register
Number of States
code
02
00
43
00
02
01
28
Num.
0x28
of
= 0b00101000
Data-
Input 67, 68, 69, 71 Off;
bytes
70, 72 ON
= 1
function-
Start Register
Number of Reg.
code
04
00
0A
00
00
04
34
00
Num.
of
Data-
bytes
= 52
CPR Touch
Modbus TCP
01
02
00
00
0x0000 (Float CD)
= 0
= 7.0
06
1A
00
00
00
Seite 15 von 19