The 'ALARM IGNORE' function deactivates the alarm for 3 days by
pressing on the heartbeat indicator. The Risycor will not trigger any
more alarms for three days, even though the alarm condition may still
be active. The bright SOS blinking of the four white LEDs turns into
regular and fast heartbeat.

9.3 CORROSION ALARM

The threshold value for the annual corrosion rate is pre-set to 24 µm
per year. If necessary, this value can be set in the provided dashboard
software (see application guideline).
A corrosion-alarm indicates that the corrosion rate at that time has
exceeded the pre-set threshold value. The damage caused to the
installation thereby depends on the value of the corrosion rate, the
frequency and/or the duration of the alarm. In an ideal situation,
the BMS should be programmed so that these conditions, possibly
combined with alarms from other Risycors in the same system, can be
sensibly passed on.
It is recommended to locate the cause of the problem and to correct
it if one of the following conditions is met:
- there have been more than 7 alarms in 7 weeks
- the alarm lasts longer than 7 days
- several Risycors in the same system give alarms at the same
time
Contact your installer / technician.