Commissioning
5 Commissioning
Following correct mounting and wiring you can put the measuring system
into operation by switching on operating voltage.
After switching on, the device initializes itself independently. The "power"
LED (green) in the sensor housing lights up. While the magnetic sensor
travels over the magnetic tape, the LEDs A and B (red) are lighting accord-
ingly.
Fig. 9: LEDs
The measuring system MSK5000+MB500/1, MR500, MBR500 is a compo-
nent of an incremental measuring system which must be referenced at a
defined position (reference point) for absolute measurement. For this pur-
pose, the reference signal must be linked to the signal of a reference value
encoder (e. g. proximity switch).
6 Travel/circumferential speeds (m/s)
Formula for calculating the travel speed:
V max.
(in m/s)
Example:
Resolution: 0.01 mm
Pulse interval: 2.5 μs
V =
MSK5000 - SA03 · Date 21.07.2020 · Art. No. 83242 · Mod. status 158/20
Power A B
Resolution in mm
=
Pulse interval in s x 1000
0.01
x 0.8 = 3.2 m/s
0.0000025 x 1000
plastic housing
1
design K
x 0.8
English
25