Kidde Excellence Serie Installationsanweisungen
Kidde Excellence Serie Installationsanweisungen

Kidde Excellence Serie Installationsanweisungen

Excellence intelligent addressable dual
Vorschau ausblenden Andere Handbücher für Excellence Serie:
Inhaltsverzeichnis
Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3
Excellence Series Intelligent Addressable Dual
Optical Detector Installation Sheet
EN DE ES FR
IT
NL PL PT SV
1
EN: Installation Sheet
Figures
Figure 1: Locking tab and status LED
(1) Locking tab
(2) Status LED
Figure 2: Inserting the detector head into the mounting base
Description
This installation sheet includes information on the 3000 Series
Intelligent Addressable Dual Optical Detectors shown in the
table below.
Model
Device type
KE-DP3120W
ODni
KE-DP3020W
ODn
The detectors use an advanced optical sensing chamber to
detect smoke.
Using dual optical wavelengths combined with multiple
detection angles, the detectors determine whether to signal a
fire alarm condition by analysing the data from the sensing
chamber to discriminate between fire and non-fire sources.
© 2023 Carrier. All rights reserved.
Description
Intelligent addressable dual
optical detector with integrated
short circuit isolator (white)
Intelligent addressable dual
optical detector (white)
2
All 3000 Series detectors support the Kidde Excellence
protocol and are compatible for use with 2X-A Series fire alarm
control panels with firmware version 5.0 or later. The detectors
are backwards compatible with 2000 Series devices.
Installation
WARNING:
Electrocution hazard. To avoid personal injury or
death from electrocution, remove all sources of power and
allow stored energy to discharge before installing or removing
equipment.
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to the
EN 54-14 standard and local regulations.
Install and wire the mounting base, as described in the
installation sheet supplied with the base.
Installing the detector head
Insert the detector head into the mounting base and rotate it
clockwise until it snaps into the locked position (see Figure 2).
The detector may be locked into the mounting base if required.
To do this, remove the locking tab before installation (see
Figure 1).
To remove a locked detector:
1.
Insert a small screwdriver into the locking tab slot
(Figure 1).
2.
Press and rotate the detector anticlockwise.
1 / 23
P/N 3102984-ML • REV 001 • ISS 29NOV23
Inhaltsverzeichnis
loading

Inhaltszusammenfassung für Kidde Excellence Serie

  • Seite 3: Regulatory Information

    Quellen zu unterscheiden. disposed of as unsorted municipal waste Alle Melder der Serie 3000 unterstützen das Kidde Excellence- in the European Union. For proper Protokoll und sind mit Brandmeldezentralen der Serie 2X-A mit recycling, return this product to your local Firmware-Version 5.0 oder höher kompatibel.
  • Seite 4: Melderempfindlichkeit

    Installation Zustand Anzeige Lokalisierter Melder [2] LED leuchtet durchgehend grün WARNUNG: Gefahr von Stromschlägen. Entfernen Sie vor der Kommunikation läuft [3] LED blinkt grün Installation oder dem Entfernen von Geräten alle [1] Nur KE-DP3120W. Energiequellen und warten Sie, bis die gespeicherte Energie [2] Bedeutet, dass über die Brandmeldezentrale der Befehl „Lokalisiere entladen ist, um Personenschäden oder Todesfälle durch Melder“...
  • Seite 5: Technische Daten

    Testen Maße und Umgebungsbedingungen Melder müssen nach der Installation immer zuerst getestet IP Nennbelastung IP20 werden, um sicherzustellen, dass der Melder mit der Kompatibler Montagesockel KE-DB3010W Brandmeldezentrale kommuniziert. Wenn der Melder nicht mit der Brandmeldezentrale kommuniziert, wurde eine Adresse Anwendung Betrieb im Innenbereich eventuell doppelt zugewiesen.