Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data; Measuring Output; Dc/Ac; [Eex Ia] Iic, 24 - Camille Bauer SINEAX TV 808-11 Betriebsanleitung

Trennverstärker
Vorschau ausblenden Andere Handbücher für SINEAX TV 808-11:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

(11)
(3)
(7)
Cami l l e Bauer AG
CH-561 0 Wohl e n
Swi t zerl a nd
Span
Zero
ON
(13) (6)
(12)
Fig. 2
(3)
Front plate
(6)
Type label
(7)
Transparent cover
(8)
Fixing bracket
(9)
Opening for withdrawing clip (for opening the housing)
Top-hat rail 35 × 15 mm or 35 × 7.5 mm (EN 50 022)
(10)
(11)
Terminals
(12)
Terminals
(13)
Space for notes
ON
Green LED for indicating device standing by

6. Technical data

Measuring input
DC current:
Standard ranges
0...20 mA, 4...20 mA, ± 20 mA
Limit values
0...0.1 to 0...50 mA
also live-zero,
start value > 0 to ≤ 50% final
value
– 0.1...0...+ 0.1 to
– 50...0...+ 50 mA
also bipolar asymmetrical
R
DC voltage:
Standard ranges
0...10 V, 2...10 V, ± 10 V
Limit values
0...0.06 to 0...40, Ex max. 30 V
also live-zero,
start value > 0 to ≤ 50% final
value
– 0.06...0...+ 0.06 to
– 40...0...+ 40 V,
Ex max. – 30...0...+ 30 V
R
16
(8)
(9)
(10)
Span
Zero
without
function
ON
= 15 Ω
i
= 100 kΩ
i
Overload:
DC current
continuously 2-fold
DC voltage
continuously 2-fold

Measuring output

DC current:
Standard ranges
0...20 mA, 4...20 mA, ± 20 mA
Limit values
0...1 to 0...20 mA
0.2...1 to 4...20 mA
– 1...0...+ 1 to – 20...0...+ 20 mA
Burden voltage:
12 V
External resistance:
R
I
AN
DC voltage:
Standard ranges
0...10 V, 2...10 V, ± 10 V
Limit values
0...1 to 0...10 V
0.2...1 to 2...10 V
– 1...0...+ 1 to – 10...0...+ 10 V
≥ 2 kΩ
Burden:
Current limiter at
Approx. 1.1 ×I
R
max.:
ext
Voltage limiter at
= ∞:
R
Approx. 13 V
ext
Residual ripple in
output current:
< 0.5% p.p.
Response time:
< 50 ms
Power supply H
AC/DC power pack (DC and 45...400 Hz)
Table 1: Nominal voltages and tolerances
Nominal voltage
Tolerance
U
N
24... 60 V
DC / AC
DC – 15...+ 33%
AC ± 15%
85...230 V
1
DC / AC
24... 60 V
DC – 15...+ 33%
DC / AC
AC ± 15%
85...230 V
± 10%
AC
85...110 V
– 15...+ 10%
DC
1
For power supples > 125 V, the auxiliary circuit should include an
external fuse with a rating ≤ 20 A DC.
≤ 1.2 W resp. ≤ 3 VA
Power input:
Accuracy data (acc. to DIN/IEC 770)
Limit error ≤ ± 0.2%
Basic accuracy:
Including linearity and reproduci-
bility errors
12 V
max. [kΩ] =
I
[mA]
ext
AN
= Output circuit full-scale value
for current output
AN
Instrument
version
Standard
(Non-Ex)
Type of protection
"Intrinsically safe"
[EEx ia] IIC

Werbung

Inhaltsverzeichnis
loading