3 Electrical connection
The unit must only be connected by a skilled electrician. The national
and international regulations for the installation of electrical equip-
ment must be observed.
Disconnect power before connecting the unit.
BN
BK
BU
4 Set-up / operation
After mounting, wiring and where necessary integration in your con-
troller check whether the unit operates correctly. If required put the
valve into all available positions and check whether the analogue out-
put operates correctly.
Operating and fault indication
LED
Description
ON = unit is ready
green
for operation
Flashes with a fre-
quency of 8 Hz =
spindle head is at
green
the limit or outside
the measuring
range *
Flashes with a fre-
quency of 8Hz =
green
fault in the
electronics **
* above or below the measuring range
** Error message cannot be terminated in contrast to the preceding
error message.
L +
Core colours:
BK: black (analogue output)
BN: brown
BU: blue
L
State analogue output
1 ... 5 V
* above the measuring
range: > 5 V
below the measuring
range: < 1V
< 1 V
Measure
Check the position
of the valve
Replace the sensor
13